– 143 –
No.
7
Part name
Replacement
of electric parts
Electrolytic
condenser
Procedure
1. Detachment
1) Carry out works of 1 of
1
,
3
and
4
.
2) Remove the lead wire connected to the terminal block.
(IPDU crossover wire)
3) Remove the connector connected to the noise filter.
(IPDU crossover wire)
4) Remove the lead wire connected to the noise filter.
(Fuse crossover wire, power supply crossover wire)
Remarks
5) Cut the bundling band which binds the upper lead of
the fan motor/lead of reactor.
6) Remove the fixing screws for the electric parts box (A).
(BT2T Ø4 × 6, 7 pcs.)
7) Remove the noise filter.
8) Remove the lead wires connected to the electrolytic
condenser. (Hexagonal bolt Ø5 × 12, 2 pcs.)
9) Remove screw of the condenser mounting band.
(BT2T Ø4 × 6, 1 pc.)
10) Remove the electrolytic condenser.
11) Mount a new electrolytic condenser.
Electric parts box (A) Terminal block
Fuse
crossover wire
Bundling band
Hexagonal bolt
Hexagonal bolt
Condenser
Condenser
mounting band
mounting band
Hexagonal bolt
Condenser
mounting band
IPDU
IPDU
crossover wire
crossover wire
IPDU
crossover wire
Power supply
crossover wire