Toshiba RAV-SM1403AT-E1 Air Conditioner User Manual


 
– 50 –
Check
code
Outdoor
LED display
Check and troubleshooting
(Item without special mention Indicates part of outdoor unit.)
[Indoor/Outdoor communication error]
[Case thermostat operation]
Check CODE No. [14].
Correct wiring of connectors
and terminal blocks.
Check outdoor P.C. board .
Defect Replace
Correct wiring indoor/outdoor
control wires
Is setting of group address
of remote controller correct?
Are inner wiring and indoor/outdoor
control wires (1, 2, 3) normal?
Are wiring of terminal blocks (1, 2, 3) normal?
YES
YES
YES
NO
NO
NO
Check crushed or broken pipe.
Defect Correct and Replace
Correct defective position.
Replace defective part.
Open valve fully.
Repair defectives position.
Recharge refrigerant.
Check outdoor P.C. board .
Defect Replace
Correct connector.
Case thermostat error Replace
Is valve fully opened?
Is PMV normal?
Is there no gas leak?
Is it not refrigerant shortage?
Is cooling/heating operation available
when short-circuiting case thermostat?
Are CN500 connection
and case thermostat normal?
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
[E04]