Toshiba RAV-SM1403AT-E1 Air Conditioner User Manual


 
– 36 –
Start of heating operation
0 10 15 c b a d [min.]
*
TE [
˚
C]
– 5
– 10
– 13
– 18
A zone
B zone
C zone
D zone
A zone
B zone
C zone
D zone
* From 10 minutes to 15 minutes after a heating operation started, the minimum value of TE is stored in
memory as TEO and the minimum temperature of TO as ToO.
At error TOAt normal TO
When status of [(TEO – TE) – (ToO – TO) 3
˚
C]
continued for 20 seconds
A zone
When status of [(TEO – TE) 3
˚
C]
continued for 20 seconds
When status of [(TEO – TE) – (ToO – TO) 2
˚
C]
continued for 20 seconds
B zone
When status of [(TEO – TE) 2
˚
C]
continued for 20 seconds
C zone When status of [TE – 18
˚
C] continued for 20 seconds
D zone When compressor operation status with TE – 13
˚
C are added by d times
SM110, SM140
a 55
b 39
c 29
d 90
11. High-pressure switch
1) When the high-pressure switch operates, the operation of the compressor is terminated.
2) The compressor restarts after 5 minutes using [1] as an error count.
After restart, the error count is cleared when operation continues for 10 minutes or more.
3) An error is confirmed with the error count [10].
4) For the indicated contents of error, confirm using the check code table.
12 Control of compressor case thermo
1) The compressor stops when the case thermo of the compressor operated.
2) When the case thermo operated for approx. 80 seconds, E04 error code (same as serial error) is
displayed on the wired remote controller. Refer to the Check Code.
3) When the case thermo is reset, the operation restarts.