Toshiba RAV-SM1104UT-E Air Conditioner User Manual


 
– 12 –
: IEC standard
<Twin type>
Revised 2: Jun., 2008
Indoor unit 1 RAV- SM564UT-E SM804UT-E SM804UT-E
Model Indoor unit 2 RAV- SM564UT-E SM804UT-E SM804UT-E
Outdoor unit RAV- SM1103AT-E SM1403AT-E SM1603AT-E
Cooling capacity (kW) 10.0 12.5 14.0
Heating capacity (kW) 11.2 14.0 16.0
Indoor unit
Power supply 1 phase 230V (220 – 240V) 50Hz
Running current (A) 14.59 – 13.38 19.17 – 17.57 21.48 – 19.69
Power consumption (kW) 3.11 4.09 4.49
Cooling Power factor (%) 98 97 95
EER 3.22 3.06 3.12
Electrical
Energy efficiency class A (B) (B)
characteristics
Running current (A) 13.36 – 12.36 18.74 – 17.18 21.20 – 19.43
Power consumption (kW) 2.93 4.00 4.43
Heating Power factor (%) 99 97 95
COP 3.82 3.50 3.61
Energy efficiency class A (B) (A)
Fan Turbo fan
Fan unit Standard air flow H/M/L (m³/min.) 17.5 / 14.5 / 13.0 20.5 / 16.0 / 13.5 20.5 / 16.0 / 13.5
Motor (W) 14 20 20
Sound pressure level H/M/L (dB•A) 32 / 29 / 28 35 / 31 / 28 35 / 31 / 28
Sound power level H/M/L (dB•A) 47 / 44 / 43 50 / 46 / 43 50 / 46 / 43
Outdoor unit
Power supply 1 phase 230V (220 – 240V) 50Hz
Standard length (m) 7.5 7.5 7.5
Min. length (m) 5 5 5
Refrigerant
Max. total length (m) 50 50 50
Refrigerant charging amount
40g/m (31m to 50m)
pipe
(Charge-less up to 30m)
Height
Outdoor lower (m) 30 30 30
difference
Outdoor higher (m) 30 30 30
Fan Propeller fan
Fan unit Standard air flow volume (m³/min.) 75 75 103
Motor (W) 63 100 100 + 100
Gas side
Main (mm) 15.9 15.9 15.9
Connecting
Sub (mm) 12.7 15.9 15.9
pipe
Liquid side
Main (mm) 9.5 9.5 9.5
Sub (mm) 6.4 9.5 9.5
Sound pressure level Cooling/Heating (dB•A) 53 / 54 54 / 54 51 / 53
Sound power level Cooling/Heating (dB•A) 70 / 71 71 / 71 68 / 70