Toshiba RAS-10SKV-E Air Conditioner User Manual


 
20
7. REFRIGERANT CYCLE DIAGRAM
7-1. Refrigerant Cycle Diagram
RAS-10SKV-E / RAS-10SAV-E
NOTE :
The maximum pipe length of this air conditioner is 10 m. The addition charging of refrigevant is
Deoxidized copper pipe
Outer dia. : 9.52mm
Thickness : 0.8mm
NOTE :
Gas leak check position
Refrigerant flow (Cooling)
Refrigerant flow (Heating)
INDOOR UNIT
T1
TO
Temp. measurement
TC
TA
Indoor heat
exchanger
Cross flow fan
Deoxidized copper pipe
Outer dia. : 6.35mm
Thickness : 0.8mm
Sectional shape
of heat insulator
Allowable height
difference : 10m
Allowable pipe length
P
Pressure measurement
Gauge attaching port
Vacuum pump connecting port
TD
4-way valve
(STF-0108Z)
Compressor
DA89X1C-23FZ
T2
Outdoor heat
exchanger
Temp. measurement
Propeller fan
Refrigerant amount : 0.63kg
OUTDOOR UNIT
Muffler
Muffler
Ø1.0 x 600
TE
Ø1.0 x 600
Min. : 1m
Chargeless : 10m
RAS-10SKV-A / RAS-10SAV-A
Max. : 10m
unnecessary because this air condition is design with charge-less specitication.
FILE NO. SVM-07008