Sunlife Enterprises DM300 Air Conditioner User Manual


 
356214-XIM-A-0108
22 Johnson Controls Unitary Products
Note 1: HACR Type per NEC.
TABLE 9: DM ELECTRICAL DATA -WITH POWERED CONVENIENCE OUTLET
MODEL
TONNAGE
VOLTAGE
COMPRESSORS
OD FAN
MOTORS
FLA EACH
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
AMPS
HEATER OPTION
MIN.
CIRCUIT
AMPACITY
(AMPS)
MAX.
FUSE/
BRKR
1
SIZE
(AMPS)
RLA
EACH
LRA
EACH
MODEL KW STAGES AMPS
15
380 9.6 62 2.1 8.3 6.3
None 0.0 - - 52.3 50
E18 11.3 1 17.1 52.3 60
E36 22.6 2 34.3 61.2 70
E54 33.8 2 51.4 82.4 90
E72 45.1 2 68.6 103.9 110
415 9.6 62 2.1 8.3 6.3
None 0.0 - - 52.3 50
E18 13.5 1 18.7 52.3 60
E36 26.9 2 37.4 65.0 70
E54 40.4 2 56.2 88.5 90
E72 53.8 2 74.9 93.1 100
20
380 20.7 130 2.1 11.7 6.3
None 0.0 - - 68.8 80
E18 11.3 1 17.1 68.8 80
E36 22.6 2 34.3 68.8 80
E54 33.8 2 51.4 86.7 90
E72 45.1 2 68.6 108.2 110
415 20.7 130 2.1 11.5 6.3
None 0.0 - - 68.8 80
E18 13.5 1 18.7 68.8 80
E36 26.9 2 37.4 69.0 80
E54 40.4 2 56.2 92.5 100
E72 53.8 2 74.9 97.1 100
25
380 22.9 145 2.1 19 6.3
None 0.0 - - 82.3 100
E18 11.3 1 17.1 82.3 100
E36 22.6 2 34.3 82.3 100
E54 33.8 2 51.4 95.8 100
E72 45.1 2 68.6 117.3 125
415 22.9 145 2.1 19 6.3
None 0.0 - - 82.3 100
E18 13.5 1 18.7 82.3 100
E36 26.9 2 37.4 82.3 100
E54 40.4 2 56.2 101.9 110
E72 53.8 2 74.9 106.5 110