Sunlife Enterprises DM300 Air Conditioner User Manual


 
356214-XIM-A-0108
Johnson Controls Unitary Products 21
Note 1: HACR Type per NEC.
TABLE 8: DM ELECTRICAL DATA -WITHOUT POWERED CONVENIENCE OUTLET
MODEL
TONNAGE
VOLTAGE
COMPRESSORS
OD FAN
MOTORS
FLA EACH
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
AMPS
HEATER OPTION
MIN.
CIRCUIT
AMPACITY
(AMPS)
MAX.
FUSE/
BRKR
1
SIZE
(AMPS)
RLA
EACH
LRA
EACH
MODEL KW STAGES AMPS
15
380 9.6 62 2.1 8.3 0.0
None 0.0 - - 46.0 50
E18 11.3 1 17.1 46.0 50
E36 22.6 2 34.3 53.3 60
E54 33.8 2 51.4 74.6 80
E72 45.1 2 68.6 96.0 100
415 9.6 62 2.1 8.3 0.0
None 0.0 - - 46.0 50
E18 13.5 1 18.7 46.0 50
E36 26.9 2 37.4 57.2 60
E54 40.4 2 56.2 80.6 90
E72 53.8 2 74.9 85.2 100
20
380 20.7 130 2.1 11.7 0.0
None 0.0 - - 62.5 80
E18 11.3 1 17.1 62.5 80
E36 22.6 2 34.3 62.5 80
E54 33.8 2 51.4 80.6 90
E72 45.1 2 68.6 100.3 110
415 20.7 130 2.1 11.5 0.0
None 0.0 - - 62.5 80
E18 13.5 1 18.7 62.5 80
E36 26.9 2 37.4 62.3 80
E54 40.4 2 56.2 84.6 90
E72 53.8 2 74.9 89.2 100
25
380 22.9 145 2.1 19 0.0
None 0.0 - - 74.7 90
E18 11.3 1 17.1 76.0 90
E36 22.6 2 34.3 76.0 90
E54 33.8 2 51.4 87.9 90
E72 45.1 2 68.6 109.4 110
415 22.9 145 2.1 19 0.0
None 0.0 - - 74.7 90
E18 13.5 1 18.7 76.0 90
E36 26.9 2 37.4 76.0 90
E54 40.4 2 56.2 94.0 100
E72 53.8 2 74.9 98.6 110