Johnson Controls Unitary Products 11
CONDENSATE DRAIN
Plumbing must conform to local codes. Use a sealing
compound on male pipe threads. Install a condensate
drain line from the one-inch NPT female connection on
the unit to an open drain.
NOTE: The condensate drain operates in a negative
pressure in the cabinet. The condensate drain
line MUST be trapped to provide proper drain-
age. See Figure 4.
COMPRESSORS
Units are shipped with compressor mountings factory-
adjusted and ready for operation.
FILTERS
Two-inch or four-inch filters can be supplied with each
unit. Filters must always be installed ahead of the
evaporator coil and must be kept clean or replaced with
same size and type. Dirty filters will reduce the capacity
of the unit and will result in frosted coils or safety shut-
down. Minimum filter area and required sizes are
shown in Physical Data Table 7.
SERVICE ACCESS
The following removable panels provide access to all
serviceable components:
Compressor compartment
Electric Heat compartment
Gas Heat compartment (Two panels)
Side Supply & Return Air compartments
(Two panels)
Blower compartment (Three panels)
Main control box
Filter compartment
Outdoor Air compartment (Two panels)
Refer to the Dimensions and Clearances Figure 13 for
location of these access panels.
FIGURE 3 - FIXED OUTDOOR AIR DAMPER
FIGURE 4 - RECOMMENDED DRAIN PIPING
Do not loosen compressor mounting bolts.
Make sure that all screws and panel latches
are replaced and properly positioned on the
unit to maintain an airtight seal.