Large Dehumidifying Dryers Controls 47
(System Backup Screen)
ACS Dryer control version 2.000 introduces a system backup feature.
Pressing SAVE SETTINGS will save the system variables for later recall.
Pressing RESTORE SETTINGS will restore previously saved values.
Pressing RESTORE FACTORY DEFAULTS will return the dryer to its factory default
state, namely:
CONVEYING:
NO CONVEYING UNITS AVAILABLE - CONVEYING DISABLED
DRYER OPTIONS:
TEMPERATURE IN FAHRENHEIT
STANDARD HEAT
OVERDRY PROTECTION DISABLED
AUTO START TIMER DISABLED
DRYER VALUES:
ALARM SILENCE DURATION 99 MIN
PASSWORD - OPERATOR 0000
PASSWORD SUPERVISOR 1234
PASSWORD OPERATOR DURATION 10 MIN
PASSWORD SUPERVISOR DURATION 10 MIN
DEWPOINT HIGH LIMIT ALARM VALUE 30 DEGF
(ALARM DISABLED)
OVERDRY SET BACK TEMPERATURE 170 DEGF
OVERDRY SET BACK SETPOINT 100 DEGF
OVERDRY SET UP TEMPERATURE 90 DEGF
PROCESS AIR TEMP. SETPOINT 180 DEGF
PROCESS AIR HI DEVIATION VALUE 35 DEGF
PROCESS AIR LO DEVIATION VALUE -35 DEGF
REGENERATION AIR SETPOINT 450 DEGF
PROCESS ACTUAL VALUE OFFSET 0.0 DEGF
REGEN ACTUAL VALUE OFFSET 0.0 DEGF