Slant/Fin XL-2000 Boiler User Manual


 
BURNER DATA—CARLIN BURNERS FOR PACKAGED BOILERS ONLY
XL-2000
11
XL-20 99-FRD 0.65 0.65 70° A DELAVAN 100 0 50 Closed
71399-00F-XL-20 0.65 70° W DELAVAN 100 0 50 Closed
XL-30 99-FRD 1.00 1.00 70° A DELAVAN 100 2 80 Closed
71399-00F-XL-30 1.15 1.00 70° A DELAVAN 130 3 90 Closed
XL-40 99-FRD 1.35 1.35 60° W DELAVAN 100 4 50 Closed
71399-00F-XL-40 1.55 1.35 60° W DELAVAN 130 4 65 Closed
XL-50 99-FRD 1.80 1.75 60° B DELAVAN 105 4 20 Open
71399-00F-XL-50 2.00 1.75 60° B DELAVAN 130 5 40 Open
BOILER
MODEL
CARLIN BURNER
MODEL (2) (3)
FIRING
RATE
NO. 2 OIL
(GPH)
SIZE
(GPH)
ANGLE
AND
TYPE
MFR.
NOZZLES
OIL PUMP
PRESSURE
SETTING
(PSIG)
“A”
APPROXIMATE
HEAD SETTING
NO.
APPROXIMATE
AIR BAND
OPENING %
(1)
SHUTTER
NON-
ADJUSTABLE
NO
TES:
(1) Single slotted air band for XL-20 and XL-30, double slotted air band for XL-40 and XL-50.
(2) See “PRECAUTIONS BEFORE STARTING OIL BURNERS” and “START-UP” on page 7 and burner figures on this page.
(3) All burner models shown are single stage.