Regency Wraps F33 Stove User Manual


 
10 Regency
®
F33-3 Freestanding Gas Stove
LOG AND EMBER INSTALLATION
WARNING: Dangerous operating conditions may occur if these
logs are not positioned in their approved locations. Read the
instructions below carefully and refer to the diagrams. If logs are
broken do not use the unit until they are replaced. Broken logs
can interfere with the pilot and burner operation.
The gas log kit contains the following:
a) Front Log
b) Rear Log
c) Small Cross Logs (2)
d) Bag of embers
e) Bag of rock wool
1) Remove the logs from the box and carefully unwrap them. The logs
are fragile, handle with care. Do not force into position.
2) Place the rear defl ector on the rear log support pins in the back of
the unit.
3) Place the rear log into the rear of the fi rebox, aligning the holes on
the underside of the log with the rear log support pins and carefully
push the log down onto the pins. See diagrams 1 and 2.
4) Ensure the front defl ector is over front log pins. See diagram 1.
5) Place the front log in the front of the unit, aligning the holes on the
underside of the log with the log support pins in the front of the
unit. Carefully push the log down onto the pins. See diagram 1.
6) Place the cross logs on top of the larger logs aligning the holes on
the underside of the cross log with the log pins in the larger logs.
See diagrams 1 & 2. Carefully push the cross logs onto the pins.
Diagram 1
TEST FOR FLUE SPILLAGE
This heater must be properly connected to a fl ue system.
WARNING: Operation of this heater when not connected to a
properly installed and maintained fl ue system or tampering with
the fl ue safety shutoff system can result in carbon monoxide (CO)
poisoning and possible death.
A “spillage” test must be made before the installed unit is left with the
customer. Follow the procedure below:
1) Start all exhaust fans in the home and then close all doors and
windows in the room.
2) Light the unit and set controls to maximum.
3) After fi ve minutes, test that there is a “pull” on the fl ue by placing
a smoke match, cigarette or similar device which gives off smoke,
on the edge of the draft hood. See Diagram below.
The smoke should be drawn into the draft hood. If the smoke is still
not drawn into the draft hood, turn the unit off and check for the cause
of the lack of draft and rectify before proceeding.
Note: If the fl ue is blocked or has a strong reverse fl ow, the thermally
actuated safety switch mounted in the draft hood will automatically
shut off the gas supply in less than 10 minutes. If the heater turns
off because of this during the spillage test, check for the cause
of the lack of draft and rectify before proceeding.
To reset the thermally actuated safety switch, let the unit cool for
10 minutes, then press the red reset button on the back of the
switch. See Diagram.
INSTALLATION