INSTALLATION
EXHAUST AND FRESH AIR INTAKE LOCATION
EXHAUST:
Base of unit to center of ue 20-5/16" (508mm)
Side of unit to center of ue 6-11/16" (170mm)
Center of unit to center of ue 5-3/4" (146mm)
FRESH AIR INTAKE:
Base of unit to center of intake 14-5/8" (356mm)
Side of unit to center of intake 11-7/16" (291mm)
Center of unit to center of intake 1" (25mm)
1"
(25mm)
11
7
/16"
(291mm)
6
11
/16"
(170mm)
14
5
/8"
(356mm)
20
5
/16"
(508mm)
5
3
/4"
(146mm)
Figure 8: Freestanding Inlet and Outlet Location.
OUTSIDE FRESH AIR CONNECTION
Outside fresh air is mandatory when installing this unit in airtight
homes and mobile homes.
A Fresh-air intake is strongly recommended for all installations.
Failure to install intake air may result in improper combustion as well as
the unit smoking during power failures.
When connecting to an outside fresh air source, do not use plastic or
combustible pipe. A 2” minimum (51 mm) ID (inside diameter) steel,
aluminum or copper pipe should be used. It is recommended, when you
are installing a fresh air system, to keep the number of bends in the pipe
to a minimum.
2" ID
(51 mm)
Optional
Elbow
Outside
Wall
Figure 9: Outside Air Connection.
Figure 10: Corner Installation.
3" (7.5 cm)
3"
(7.5 cm)
Fresh Air Intake
Wall thimble
manufactured
by pellet vent
manufacturer.
CORNER THROUGH WALL INSTALLATION
INSTALLATION
INSTALL VENT AT CLEARANCES SPECIFIED BY THE VENTING
MANUFACTURER.