Greenfi re Pellet Stove and Insert Technical Manual
14
INSTALLATION
OUTSIDE VERTICAL INSTALLATIONS
To accomplish a outside vertical pipe installation, follow steps 1 through 5
in the "Inside Vertical Installation" section and then fi nish it by performing
the following (refer to Figure 16).
1. Install a tee with clean out on the outside of the house.
2. Install PL vent upward from the tee. Make sure that you install support
brackets to keep the vent straight and secure.
3. Install ceiling thimble and secure the fl ashing as you go through the
roof.
4. Ensure that the rain cap is approximately 24” (610 mm) above the
roof.
Rain cap
Flashing
24"
(61 cm)
3"
(7.5cm)
Tee with
cleanout
Fresh air
intake
3" (7.5 cm)
Clearance
Support
bracket
Type "L", "PL" or
all fuel vent
Figure 16: Outside Vertical Installation.
HEARTH MOUNT INSTALLATION
1. Lock fi replace damper in the open position.
2. Install a positive fl ue connector at the fi replace dampers.
3. Connect a clean-out tee or a 90° elbow to the exhaust pipe.
4. Install fl exible stainless steel liner or listed pellet vent to the top of the
chimney.
Floor
Protection
Combustible FloorMasonry Fireplace
Min 6"
(150 mm)
Mantel
Minimum 8" (20 cm)
from top of stove
Damper Removed
or Fastened Open
Clean-out
Fresh-air intake
should com from
chimney. If holes
a
lready exist fresh-air
intake can be taken
through back of the
fireplace or through
the ash dump.
Figure 17: Hearth Mount - Side View.
INSTALLATION