Raypak B6000 Boiler User Manual


 
Page 9
AIR TEMPERATURE SENSOR
INSTALLATION
Fig. #9040
TYPICAL AIR TEMPERATURE SENSOR
Air Temperature Sensor Installation Notes:
Locate on coldest side of building, usually (North or West) side.
Install the sensor in a shaded area, out of direct sunlight.
Locate no higher than 2/3 way up side of building or between 2nd and 3rd floor if building
is more than 3 stories tall.
Shielded cable length not to exceed 4000 feet.
Do not locate under an overhang, near wall corners, near drafts from stacks, air
moving devices, windows, doors, or balconies.
Assure cable length does not exceed 4000 ft. Use larger gauge (Belden #9842)
cable if run is in excess of 100 ft.
Install in conduit with no other wiring.
Observe proper wire colors. Sensor is polarity sensitive.