Raypak B6000 Boiler User Manual


 
Page 21
SYSTEM CONTROL/DISPLAY FAMILIARIZATION
The System is set up by using the selector buttons and the displays on the System Control
module.
There are ten or more displays. Each display provides information regarding the system
operating parameters and system component status. Some displays provide information
only, such as current outdoor temperature, system temperature, etc..
Selectable data is identified by flashing characters.
The selector buttons are:
"MENU" - which when pressed will change displays.
"SELECT" - moves the cursor - flashing character - to the next selection in a display.
"+" - moves a value to a higher reading (e.g. Display shows flashing boiler #1. Pushing
"+" will change display to boiler #2).
"–" - moves a value to a lower position (e.g. Display shows flashing boiler #2. Pushing
"–" will change display to boiler #1).
EDITING B6000 DISPLAYS LOCATION
The B6000 BMS has a forty (40) character screen that displays status and memory contents.
Selectable Parameters on the B6000 Monitor Screen are as follows:
Selectable Parameters Range Value
Change to Fahrenheit (F) or Celsius (C). Default (After Initialization)
Maximum Water Temp 70 - 235 Degrees…………180
Set 40 - 220 Degrees…………100
Day Temperature 40 - 220 Degrees…………100
Nite 40 - 220 Degrees………… 90
Ratio None - 20:1 Numeric…………1.0:1
° Rise 1 - 99 Degrees………… 20
Step 1s,2s, 5 - 100 Percentile……… 20
O/C (Outdoor Cutoff) 35 - 199 Degrees………… 65
O/Cdb (O/C dead band) 1 - 9 Degrees………… 4
CBand (Control Band) 1 - 9 Degrees………… 3
Lead 1 - 8 Numeric………… 1
Change Hours 0 - 225 Numeric…………100
Pump Delay * 0 - 20 Minutes………… 3
Ign Time* 15 - 100 Seconds………… 30
*Indicates multiple entries
When the B6000 BMS is equipped with a night setback feature, [ WHEN INITIALIZED],
NITE SETBACK defaults to OFF.