Page 48
The procedures outlined below assume that the initial
installation / turn on / power up procedures have been
completed and that the B6000 was operational. This
guide is a basic instruction to determine if an authorized
Raypak representative should be contacted.
If you follow the instructions in this manual and have
difficulty operating the B6000, locate the SYMPTOM in
the left column below. Check the corresponding POS-
SIBLE CAUSE and CORRECTIVE ACTION Column to
locate and remedy the problem.
Troubleshooting Guide
Symptom
No Display.
* Nite set-back time display no
longer correct.
* Nite set-back not working
properly.
* Time display does not maintain
proper time.
System not working automatically.
Display shows incorrect number of
boilers.
Scrambled control display.
Boiler does not function properly
after power outage.
Boiler "Not on Line" displayed.
Outdoor and water temp.
readings Incorrect (-35°F).
Displayed parameters
do not make sense.
System Faults indicators do not
make sense.
* With Nite Set-Back option only.
Possible Cause
No Primary power.
Time display accidentally
Re-Programmed.
Nite set-back turned off.
Clock times not set.
System ground not adequate.
Line noise.
Internal battery weak.
Prolonged power outage.
Boiler monitor has Manual Mode
selected
Inadequate grounds.
Line noise
Power outages.
Power outages.
Internal battery weak.
Line noise.
System ground not adequate.
Primary power at boiler not
connected.
Inadequate ground
Line noise.
Power outage.
Power outage.
Power outage.
Corrective Action
Check power connections to units.
Check surge protection devices.
Check disconnects, check
grounds.
Check power switches.
Initialize system.
Program Nite set-back feature.
Initialize system.
Initialize system and / or
contact authorized Raypak
Representative for further instruc-
tions.
Select Automatic mode on Boiler
Monitor.
Check primary power - check
wired ground.
Rework as necessary.
Initialize system.
Initialize system.
Initialize system.
Initialize system.
Initialize system.
Initialize system.
Initialize system.