Quadra-Fire 31M-ACC-GT Stove User Manual


 
Page 6
7033-277C
March 2, 2007
R
3100 Wood Stove Series (ACC)
Recommended
Location
Marginal
Location
Location
Not
Recommended
Recommended
Location
Location NOT
Recommended
Multi-level Roofs
Windward
Leeward
Outside Termination Cap
Figure 6.1
C. Negative Pressure
Draft is the pressure difference needed to vent appliances
successfully. Considerations for successful draft include:
Preventing negative pressure
Location of appliance and chimney
Negative pressure results from the imbalance of air avail-
able for the stove to operate properly. Causes for this imbal-
ance include:
Exhaust fans (kitchen, bath) etc.)
Range hoods
Combustion air requirements for furnaces, water
heaters and other combustion appliances
Clothes dryers
Location of return-air vents to furnace or air condi-
tioning
Imbalances of HVAC air handling system
Upper level air leaks
Recessed lighting
Attic hatch opening
Duct leaks
To minimize the affects of negative air pressure the following
must be considered:
Install the outside air kit. Install the intake on the
side of the house towards prevailing winds during the
heating season.
Ensure adequate outdoor air is supplied for combus-
tion appliances and exhaust equipment.
Ensure furnace and air conditioning return vents are
not located in the immediate vicinity of the appli-
ance,
Avoid installing the appliance near doors, walkways
or small isolated spaces.
Recessed lighting should be of “sealed can” design;
attic hatches weather stripped or sealed; and attic
mounted duckwork and air handler joints and seams
taped or sealed.
WARNING
Negative pressure can cause spillage of com-
bustion fumes, soot and carbon monoxide.
Appliance needs to draft properly for safety.
Asphyxiation Risk.