3100 Wood Stove Series (ACC)
R
D. Chimney Termination Requirements
Follow manufacturers instructions for clearance, securing,
fl ashing and terminating the chimney.
• Must have an approved and listed cap
• Must not be located where it will become plugged by
snow or other material
• Must terminate at least 3 feet (91cm) above the roof
and at least 2 feet (61cm) above any portion of the
roof within 10 feet (305cm).
• Must be located away from trees or other struc-
tures
These are safety requirements and are not meant to assure proper fl ue draft.
Figure 19.1
E. 2-10-3 Rule
Figure 19.2
NOTE:
• Chimney performance may vary.
• Trees, buildings, roof lines and wind conditions affect
performance.
• Chimney height may need adjustment if smoking or
overdraft occurs.