Napoleon Fireplaces GDS26N Indoor Fireplace User Manual


 
20
W415-0607 / A / 01.18.08
FIGURE 34
MINIMUM MANTEL, SHELF OR CEILING CLEARANCES
1”
2”
47
1
/2
35
1
/2
5”
BRICK
COMBUSTIBLE NON-COMBUSTIBLE
29
1
/8” MINIMUM
PLUS RISE *
0” IF
NON-COMBUSTIBLE
FINISHING IS USED
SUCH AS BRICK
AND STONE.
12”
MANTEL, SHELF,
OR CEILING
REAR EXIT TOP EXIT
* HORIZONTAL VENT SECTIONS: A minimum clearance of 1"
at the bottom and sides and 2" at the top of the vent pipe in all
horizontal runs to combustibles is required. Use restop spacer
W010-1313 and shield W585-0240 (supplied).
* VERTICAL VENT SECTIONS: A minimum of 1" all around the
vent pipe on all vertical runs to combustibles is required. Use
restop spacer W010-1313 (supplied).
The stove requires a minimum ceiling height
of 47 1/2" for a rear vent. For temperature
requirements, the space around and above the
stove must be left unobstructed.
5”
BRICK
COMBUSTIBLE NON-COMBUSTIBLE
45
1
/2” MINIMUM
PLUS RISE *
MANTEL, SHELF,
OR CEILING
0” IF
NON-COMBUSTIBLE
FINISHING IS USED
SUCH AS BRICK
AND STONE.
1”
2”
15
1
/2
35
1
/2
51”
2”
The stove requires a minimum ceiling height of
51" for a top vent. For temperature requirements,
the space around and above the stove must be
left unobstructed.
FIGURE 35
Minimum clearance to combustible construction from
stove and vent surfaces:
A - 2"
B - 5"
C - 2"
- 1" to bottom and sides of the vent pipe*
- 2" to top of the vent pipe*
Rear Exit
- 47 1/2" to ceiling from base of the unit
Top Exit
- 51" to ceiling from base of the unit
MINIMUM CLEARANCES TO COMBUSTIBLES
BACK WALL
SIDE WALL
BACK WALL
SIDE WALL