Napoleon Fireplaces GDS26N Indoor Fireplace User Manual


 
12
W415-0607 / A / 01.18.08
V
1
V
2
90°
45°
90°
90°
Simple venting con guration (only two 90° elbows)
Example 5:
V
1
= 4 ft
V
2
= 1.5 ft
V
T
=
V
1
+
V
2
=
4 + 1.5 = 5.5 ft
H
1
= 2 ft
H
2
= 1 ft
H
3
= 1 ft
H
4
= 1.5 ft
H
R
= H
1
+ H
2
+ H
3
+ H
4
= 2 + 1 + 1 + 1.5 = 5.5 ft
H
O
= .03(four 90° elbows + one 45° elbow - 90°)
= .03(90 + 90 + 90 + 90 + 45 - 90) = 9.45 ft
H
T
= H
R
+ H
O
= 5.5 + 9.45 = 14.95 ft
H
T
+ V
T
= 14.95 + 5.5 = 20.45 ft
Formula 1: H
T
< 3.5V
T
3.5V
T
=
3.5 x
5.5 = 19.25 ft
14.95 < 19.25
Formula 2: H
T
+ V
T
< 24.75 feet
20.45 < 24.75
Since both formulas are met, this vent con guration is
acceptable.
FIGURE 15
For vent con gurations requiring more than two 90° elbows
the following formulas apply:
Formula 1: H
T
< 3.5V
T
Formula 2: H
T
+ V
T
< 24.75 feet
HORIZONTAL VENT RUN PLUS OFFSETS IN FEET
H
T
See graph to determine the required vertical rise V
T
for the
required horizontal run H
T
FIGURE 14
The shaded area within the lines represents acceptable
values for H
T
and V
T
.
REAR EXIT / HORIZONTAL TERMINATION
H
3
H
4
90°
REQUIRED
VERTICAL
RISE IN
INCHES
V
T
0
10
51525
100
50
150
3.5 19.2512.5
12
63
147
1
H
1
H
2
(H
T
) > (V
T
)