Napoleon Fireplaces GDI30 Indoor Fireplace User Manual


 
23
W415-0806 / 06.28.09
10.0 TROUBLE SHOOTING
!
WARNING
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RAN OUT,
WITH THE GLASS DOOR OPEN OR REMOVED.
SYMPTOM PROBLEM TEST SOLUTION
Main burner goes out; pilot
stays on.
Pilot ame is not large
enough or not engul ng the
thermopile.
- Turn up the pilot ame.
- Replace pilot assembly.
Thermopile shorting. - Clean thermopile connection tot he valve. Reconnect.
- Replace thermopile / valve.
Remote wall switch wire is too
long; too much resistance in
the system.
- Shorten wire to connect length or wire gauge.
Faulty thermostat or switch. - Replace.
Main burner goes out; pilot
goes out.
Refer to “MAIN BURNER GOES OUT; PILOT STAYS ON”
Vent is blocked - Check for vent blockage.
Vent is re-circulating - Check joint seals and installation
Flexible vent has become
disconnected from appliance.
- Re-attach to appliance.
- Cap was not replaced.
Pilot goes out when the
gas knob is released.
The gas valve has an
interlock device which
will not allow the pilot
burner to be lit until
the thermocouple
has cooled. Allow
approximately 60
seconds for the
thermocouple to cool.
System is not correctly
purged.
- Purge the gas line.
Out of propane gas. - Fill the tank.
Pilot ame is not large
enough.
- Turn up the pilot ame.
Pilot ame is not engul ng the
thermocouple
- Gently twist the pilot head to improve the ame pattern
around the thermocouple.
Thermocouple shorting / faulty. - Loosen and tighten thermocouple.
- Clean thermocouple and valve connection.
- Replace thermocouple.
- Replace valve.
Faulty valve. - Replace.
Pilot burning; no gas to
main burner; gas knob
is on ‘HI’; wall switch /
thermostat is on.
Thermostat or switch is
defective
- Connect a jumper wire across the wall switch terminals;
if main burner lights, replace switch / thermostat.
Wall switch wiring is defective. - Disconnect the switch wires & connect a jumper wire
across terminals 1 & 3; if the main burner lights, check
the wires for defects and/or replace wires.
Main burner ori ce is plugged. - Remove stoppage in ori ce.
Faulty valve. - Replace.
Pilot will not light. No spark at pilot burner. - Check if pilot can be lit by a match.
- Check that the wire is connected to the push button
igniter.
- Check if the push button igniter needs tightening.
- Replace the wire if the wire insulation is broken or
frayed.
- Replace the electrode if the ceramic insulator is cracked
or broken.
- Replace the push button ignitor
Out of propane gas. - Fill the tank.
Spark gap is incorrect. - Spark gap should be 0.150” to 0.175” (5/32” to 11/64”
approx.) from the electrode tip and the pilot burner. To
ensure proper electrode location, tighten securing nut
( nger tight plus 1/4 turn).
No gas at the pilot burner. - Check that the manual valve is turned on.
- Check the pilot ori ce for blockage.
- Replace the valve.
- Call the gas distributor.
42.3
PILOT
BURNER
THERMOCOUPLE
THERMOPILE