Napoleon Fireplaces GDI30 Indoor Fireplace User Manual


 
11
W415-0806 / 06.28.09
3.0 FRAMING
Combustible mantel clearance can vary according to the mantel depth. Use the graph to help evaluate the
clearance needed. These same requirements apply to any combustibles protruding on either side of the appli-
ance.
3.1 MINIMUM MANTEL CLEARANCES
!
WARNING
RISK OF FIRE, MAINTAIN ALL SPECIFIED AIR SPACE CLEARANCES TO COMBUSTIBLES. FAILURE
TO COMPLY WITH THESE INSTRUCTIONS MAY CAUSE A FIRE OR CAUSE THE APPLIANCE TO
OVERHEAT. ENSURE ALL CLEARANCES (I.E. BACK, SIDE, TOP, VENT, MANTEL, FRONT, ETC.) ARE
CLEARLY MAINTAINED.
WHEN USING PAINT OR LACQUER TO FINISH THE MANTEL, THE PAINT OR LACQUER MUST BE
HEAT RESISTANT TO PREVENT DISCOLOURATION.
This insert must be recessed into a vented noncombustible wood-burning appliance (prefabricated or masonry)
only. The minimum appliance opening size in which the appliance is to be installed is:
HEIGHT 21.75" WIDTH 28" DEPTH 18"
The minimum allowable chimney ue size is 6" round.
The minimum distance, from the bottom of a combustible mantle projecting 3" maximum from the wall to the
top of the louvre opening, is 12".
MINIMUM CLEARANCE TO COMBUSTIBLES MUST BE MAINTAINED OR A SERIOUS FIRE HAZARD
COULD RESULT.
NEVER OBSTRUCT THE FRONT OPENING OF THE APPLIANCE.
!
WARNING