Napoleon Fireplaces Fireplace Indoor Fireplace User Manual


 
8
W415-0619 / B / 03.03.08
TYPICAL VENT INSTALLATIONS - VERTICAL TERMINATION
24”
MIN.
MINIMUM
VERITICAL
4”
MIN.
FIGURE 3a
24”
MIN.
MINIMUM
VERITICAL
MAXIMUM
HORIZONTAL
5 FT MAX.
15 FT
MAX.
4”
MIN.
MAXIMUM
VERTICAL
19 1/2 FT
MAX.
4”
MIN.
MIN MAX FIGURE
Allowable 3” vent connections (excluding replace and air terminal connections) N/A 2
Rise per foot (recommended) 1/4” N/A
Rise per foot (allowable) 0” N/A
Vertical run (when not venting horizontally) 24” 19 1/2 FT 3a, 3c
Horizontal run 4” 5 FT 3a, 3b, 3c
FIGURE 3b
FIGURE 3c
0
1 2 3 4 5 6 7 8 9 10
20
HORIZONTAL VENT RUN PLUS OFFSET IN FEET (HT)
REQUIRED
VERTICAL
RISE IN
FEET (VT)
18
16
14
12
10
8
6
4
2
19.5
15
1.33
See graph to determine the required vertical rise V
T
for the required
horizontal rise H
T
.