Napoleon Fireplaces Fireplace Indoor Fireplace User Manual


 
10
W415-0619 / B / 03.03.08
INSTALLATION / FRAMING
WALL AND CEILING PROTECTION
This application occurs when venting through an exterior
wall. Having determined the air terminal location, cut and
frame a hole in an exterior wall with a minimum square
opening of 8” wide x 8” high.
1. Apply a bead of caulking all around and place the restop
spacer over the framework to restrict cold air from being
drawn into the room or around the replace. Ensure that the
spacer maintains the required clearance to combustibles.
Secure the spacer in place using the 4 longer screws
supplied. Once the vent pipe is installed in its nal position,
apply high temperature sealant (not supplied) between the
pipe and the restop spacer.
FIGURE 5
This application occurs when venting through a roof. Installation kits for various roof pitches are
available from your Napoleon® dealer. See Accessories to order the speci c kit required.
1. Determine the air terminal location, cut and frame a 8” square opening in the ceiling
and the roof to provide the minimum clearance between the vent pipe and any combustible
material. Try to center the vent pipe location midway between two joists to prevent having to
cut them. Use a plumb bob to line up the center of the openings.
Do not ll this space with any type of material.
A vent pipe shield will prevent any materials such as
insulation, from lling up the 1" air space around the
pipe. Nail headers between the joist for extra support.
2. Apply a bead of caulking (not supplied) to the
framework or to the Wolf Steel vent pipe shield plate or
equivalent (in the case of a nished ceiling), and secure
over the opening in the ceiling. A restop must be placed
on the bottom of each framed opening in a roof or ceiling
that the venting system passes through. Apply a bead of caulking all around and place a
restop spacer over the vent shield to restrict cold air from being drawn into the room or
around the replace. Ensure that both spacer and shield maintain the required clearance
to combustibles. Once the vent pipe is installed in its nal position, apply sealant between
the pipe and the restop assembly.
3. In the attic, slide the vent pipe collar down to cover up the open end of the shield and tighten. This will prevent any
materials, such as insulation, from lling up the 1" air space around the pipe.
VERTICAL INSTALLATION
FIGURE 6
FIRESTOP
UNDERSIDE OF JOIST
8”
SHIELD
8”
FIGURE 7
FIGURE 8
VENT
PIPE
COLLAR
VENT PIPE
SHIELD
CAULKING
VENT PIPE
SHIELD
CAULKING
HIGH
TEMPERATURE
SEALANT
8”
8”
FIRESTOP
SPACER
INSIDE
OUTSIDE