Mitsubishi Electronics PUZ-A42NHA2-BS Air Conditioner User Manual


 
8
Service Ref.
PUY-A12NHA2 PUY-A18NHA2 PUY-A24NHA2 PUY-A30NHA2 PUY-A36NHA2 PUY-A42NHA2
PUY-A12NHA2-BS PUY-A18NHA2-BS PUY-A24NHA2-BS PUY-A30NHA2-BS PUY-A36NHA2-BS PUY-A42NHA2-BS
Power supply
Phase Single
Cycle 60Hz
Voltage 208/230V
MCA A131318252526
MOCP A 15 20 30 40 40 40
Breaker size A 15 15 25 30 30 30
External finish Munsell 3Y 7.8/1.1
Heat exchanger Plate fin coil
Defrost method -
Crankcase heater
kW
-
Compressor Hermetic
Model SNB130FPBM1 SNB130FPBM1 TNB220FLDM TNB220FLDM TNB220FLDM ANV33FDJMT
Motor output kW 0.85 0.85 1.3 1.3 1.3 2.5
R.L.A. 12 12 12 12 12 20
L.R.A. 14 14 14 17.5 17.5 27.5
Starter type Inverter
Fan
Fan (drive) o No.
Propeller fan
o
1 Propeller fan
o
1 Propeller fan
o
1 Propeller fan
o
1 Propeller fan
o
1 Propeller fan
o
2
Fan motor output
kW
0.040 0.040 0.075 0.075 0.075 0.086 + 0.086
Fan motor
F.L.A.
0.35 0.35 0.75 0.75 0.75 0.40 + 0.40
Airflow m
3
/min 34 34 55 55 55 100
CFM 1200 1200 1940 1940 1940 3530
Sound level Cooling dB 46 46 48 48 48 51
Heating dB
Protection devices HP switch HP switch HP switch HP switch HP switch HP switch
LP switch
Discharge thermo Discharge thermo Discharge thermo Discharge thermo Discharge thermo Discharge thermo
Dimension W mm 800 800 950 950 950 950
D mm 300+23 300+23 330+30 330+30 330+30 330+30
H mm 600 600 943 943 943 1350
W in. 31-1/2 31-1/2 37-12/32 37-12/32 37-12/32 37-12/32
D in. 11-13/16 + 7/8 11-13/16 + 7/8 13 + 1-3/16 13 + 1-3/16 13 + 1-3/16 13 + 1-3/16
H in. 23-5/8 23-5/8 37-1/8 37-1/8 37-1/8 53-5/32
Weight kg 41 44 74 74 74 117
lbs 90 97 163 163 163 258
Refrigerant R410A
Charged kg 1.3 1.7 2.7 2.7 2.7 4.5
lbs 2 +14/16 3 + 12/16 6 6 6 10
Control Linear expansion valve
Oil Model Ester
(
MEL56
)
Charged L 0.65 0.65 0.87 0.87 0.87 1.4
Ether
(
FV50S
)
oz 20 20 28 28 28 45
Refrigerant Pipe size OD mm 6.35 6.35 9.52 9.52 9.52 9.52
piping Liquid in. 1/4 1/4 3/8 3/8 3/8 3/8
Pipe size OD mm 12.7 12.7 15.88 15.88 15.88 15.88
Gas in. 1/2 1/2 5/8 5/8 5/8 5/8
Connection method Indoor Flared
Connection method Outdoor
Flared
Height difference m Max. 30 Max. 30 Max. 30 Max. 30 Max. 30 Max. 30
IU - OU ft Max. 100 Max. 100 Max. 100 Max. 100 Max. 100 Max. 100
Piping length m Max. 30 Max. 30 Max. 50 Max. 50 Max. 50 Max. 50
ft Max. 100 Max. 100 Max. 165 Max. 165 Max. 165 Max. 165
OCH429--1.qxp 07.11.20 9:17 AM Page 8