Millennium Enterprises MLP-A/AR Carbon Monoxide Alarm User Manual


 
Net Safety Monitoring Inc
MLP-A/AR/AD-ST1400-25 2
STEP 1 — PLAN
LOCATE CONTROLLER/SENSOR
Prior to the installation process, a location plan for placing the Controller and
Sensor should be developed. Although there are no absolute rules for
determining the quantity and location of a sensor or controller, the following
points should be considered when planning the installation.
Locate the Controller where it will be accessible and visible.
Oxygen deficiency can be caused by O2 consumption from such activities as
chemical reactions or combustion and/or displacement by other gases.
Use redundant systems to enhance protection and reliability.
Consider air movement patterns within the facility.
Seek advice from experts knowledgeable about the primary gas to be
detected.
Use common sense and refer to various regulatory publications that discuss
general guidelines for your industry.
The two most common installation options are as follows.
Option 1
Locate Sensor separate from Controller using a certified (Net Safety Muti-propose)
Junction Box.
The Controller is located near eye-level. Conduit is run from the Controller to
the Sensor. The Multi-purpose Junction Box is used to connect the conduit from
the Controller to the Sensor. A Calibration Cup can be attached to the Sensor.
Tubing can be run from the calibration cup to a convenient location accessible
for calibration gas to be injected. Refer to MAN-0081 for Multi-purpose Junction
Box Terminal designations.
Option 2
The Sensor is attached directly to the Controller. A Calibration Cup and tubing
may also be used to facilitate calibration as in Option 1 above.
See "Sensor and Controller" on page 6 for detailed instructions.
Figure 1: Locate Sensor/Controller
TIP:
The Calibration Cup allows for tubing to be affixed
to a Sensor mounted in remote locations. The tubing
is directed to a level, usually close to the Controller,
for easy injection of calibration gas.
The Calibration Cup can also act as a splash guard,
protecting sensors when mounted low to the ground.
Sensor
Conduit to
Controller
Apply Calibration Gas
Controller
Calibration Cup
About
eye
level
CCS-1