Honeywell R4795A Home Safety Product User Manual


 
3 60-2285—7
R4795A
SPECIFICATIONS
TERMINAL RATINGS:
Terminal Load Rating
3 Pilot Valve 125 VA pilot duty.
Intermittent Ignition
a
360 VA.
4 Interrupted Ignition 360 VA.
5 Main Fuel Valve(s) 125 VA pilot duty, or 25 VA pilot duty plus one or more motorized
valves with total rating up to 400 VA opening, 200 VA holding.
6-7 Airflow Switch 0.6A at 30 Vdc.
8 Fan or Burner Motor 9.8A full load, 58.8A locked rotor (inrush) at 120 Vac. 4.9A full
load, 29.4A locked rotor (inrush at 220 and 240 Vac.
Isolated Spdt Alarm
Terminals (Optional)
Alarm 3A at 24 volts, or 1A at 120 volts, in a suitable wiring enclosure.
a
When ignition is connected to terminal 3, terminal 4 cannot be used.
NOTE: Allowable inrush can be up to ten times the pilot
duty rating.
Example:
Pilot duty rating = 125 VA.
At 120V, running current is 125/120 = 1.05A.
Maximum allowable inrush is 10 times 1.05 = 10.5A.
DIMENSIONS (Includes Cover and Subbase): Approxi-
mately 5 x 5 x 5 in. (127 x 127 x 127 mm).
MOUNTING: Q270A1024 Subbase. Ordered separately.
APPROVALS:
Underwriters Laboratories Inc Listed: 120V models us-
ing 30, 60, or 90 second prepurge timers including –
40°F (–40°C) rated models; file no. MP268, guide
no. MCCZ.
Underwriters Laboratories Inc. Component Recognized:
120 volt models using 7 or 10 second prepurge timers
including -40°F (-40°C) rated models; file no. MP268,
guide no. MCCZ2.
Canadian Standards Association Certified: 120V mod-
els only, including -40°F (-40°C) rated models; file
no. LR95329.
Factory Mutual Approved: R4795A 120V models; re-
port no. 18774. -40°F (-40°C) rated models; report
no. 19608.1.
American Gas Association Design Certified: File no. 21-6
(F and F1).
ACCESSORIES:
W136A Test Meter (includes 117053 Meter Connector
Plug).
Flame Simulator:
203659 Ultraviolet
121708 Rectification
123514B Ultraviolet
117053 Meter Connector Plug
FSP1535 Tester for operational check
Q624 Solid State Spark Generator
118702E Remote Reset Cover, 120 Vac, 60 Hz
202471C Reset Cover for R4795A
ADDITIONAL CONTROLS:
Order all additional controls separately:
Q270A1024 Mounting Subbase.
Plug-In Flame Signal Amplifiers, Rectification Type
(Green Backplate): For use with C7004B C7005A,
and B, C7008A, or Q179A,C Rectifying Flame Rods
(for gas); C7003A, C7010A, C7013A or C7014A
Photocells (for oil); or C7012A,C Purple Peeper Ul-
traviolet Flame Detectors (for gas or oil).
R7289A1004 Amplifier: 3 sec nominal flame failure
response.
R7289A1012 Amplifier: 0.8 sec nominal flame failure
response.
R7289A1020 Amplifier: 3 sec nominal flame failure
response, -40°F (-40°C) ambient temperature.
Ultraviolet Type (Purple Backplate): For use with C7027A,
C7035A or C7044A Minipeeper Ultraviolet Flame
Detectors (for gas or oil).
R7290A1001 Amplifier: 3 sec nominal flame failure
response.
R7290A1019 Amplifier: 0.8 sec nominal flame failure
response.
R7290A1027 Amplifier: 3 sec nominal flame failure
response, -40°F (-40°C) ambient temperature.
ST71A Plug-In Prepurge Timer (ordered separately):
Minimum Timings: 7, 10, 30, 60, and 90 seconds (as
ordered).
Maximum Timings: 8.4, 12, 36, 72, and 108 seconds
at room ambient temperature.
Recommended Limits: L404A; L604A,L; L4006A,C,E;
L4008A,E,F; L6006A,B: These controllers were
Underwriters Laboratories Inc. tested for breaking
loads only, at 120 Vac, for the total rating of 9.8A
full load, plus 360VA ignition, plus 250 VA pilot
duty.
Flame Detector: As specified in Plug-In Flame Signal
Amplifiers listed above.