Honeywell IPGSM-DPC Smoke Alarm User Manual


 
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide
13
RF Specifications
Band
Transmission
Frequency
(MHz)
Transmit
Power
(dBm)
Receive
Frequency
(MHz)
Receive
Sensitivity
(dBm)
Number
of
Channels
Channel
Spacing
(MHz)
Duplex
Separation
(kHz)
GSM 850
824-849 33 869-894 -107 124 200 45
GSM 900
890-915 33 935-960 -107 124 200 45
GSM 1800
1710-1785 30 1805-1880 -106 374 200 95
GSM 1900
1850-1910 30 1930-1990 -105.5 299 200 80
Central Station Messages
Alarm Condition Alarm Code Restore Code
Power On / Reset E339 C0803 N/A
Power Loss E337 C0803 R337 C0803
Low Battery E338 C0803 R338 C0803
Battery Charger Failure E314 C0803 R314 C0803
ECP Supervision (Compromise Indication)
E355 C0000 R355 C0000
Primary Communication Path Supervision E350 C0951 R350 C0951
Secondary Communication Path Supervision E350 C0952 R350 C0952
Periodic Comm Test Fail E358 C0803 R358 C0803
Test 5555 5555 9 N/A
Specific to RESIDENTIAL / COMMERCIAL Control Panels (Such as the VISTA-10P, 15P,
and 20P series.)
UL: The information provided in this section for the VISTA-10P, 15P, and 20P series control
panels has not been evaluated with this communications module.
Communicator Trouble (low battery, ECP bus,
network) (Possible Compromise Indication)
E353 C0803 R353 C0803
Radio Fault E353 C0103 R353 C0103
Specific to COMMERCIAL Control Panels (Such as the VISTA-128/250 series.)
Communicator Trouble (low battery, ECP bus,
network) (Possible Compromise Indication)
E333 C0803 R333 C0803
Radio Loss of Signal
(Possible Compromise Indication)
E357 C0803
R357 C0803 or
R380 C0803
Radio Fault (low battery, tamper, ECP Bus) E333 C0803 R333 C0803
AlarmNet Messages
Communication failure.
(Possible Compromise Indication)
5555 1555 6 5555 3555 6
Authorized Radio Substitution 00D0 010C 0 N/A
Unauthorized Radio Substitution Attempt 00D0 010E 0 N/A
Service Termination 00D0 020E 0 N/A