Honeywell IPGSM-DPC Smoke Alarm User Manual


 
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide
10
Dialer Capture Module Information
LED Indicator STATUS
RED – Steady ON Messages exist in buffer.
RED – Flashing No messages to be sent. Waiting for messages.
GREEN – Steady ON Normal Indication.
GREEN – Blinks every 2 sec. PowerBoost1 communication problem.
GREEN – Blinks twice every sec. Communication Module connection is lost.
GREEN – Blinks 10 times every sec. PowerBoost1 and Communications Module connection is lost.
iPGSM-COM-004-V0
Dialer Capture Module
Telco 1
Telco 2
ECP
Tip 2
Ring 2
ZN-
EOL
EOL
ZN+
PWR
GND
Tip 1
Ring 1
Data Out
Data In
12V In
GND
RED
GREEN
LED Display Information
Panel Status LED Indicator
RADIO TROUBLE Yellow – ON when radio trouble is present.
Both IP and GSM communication paths are lost.
Communicator radio is not registered.
Old Alarm Time has been exceeded. (Message has not been
delivered within the fixed 10 minute window.)
Buzzer – Upon loss of AC power, this will beep once every 10
seconds.
LOW BATTERY Yellow – ON when battery is low (<11.5VDC).
Yellow – (not used)
AC LOSS Yellow – ON when no AC is present (< 90VAC).
AC ON Green – ON when AC is present.
Note: If a wire pulled out of the LED Board Connector
refer to the diagram on right and reinsert wire, ensuring
the connector pin is locked in.
Note: Telco ports 1 (primary dialer)
and 2 (secondary dialer) may be
used instead of the terminal board.
Whichever connection method is
used, both Telco paths must be
connected to the Fire Panel.
NC
NC
LED Board
Connector
Wires
Violet
Black
White
Red
Brown
Yellow
Gray
buzzer
RADIO TROUBLE
LOW BATTERY
AC ON
(not used)
AC LOSS