Honeywell IPGSM-DP Smoke Alarm User Manual


 
Wiring Diagram
The wiring diagram below is depicted for point-to-point electrical connection checks used for troubleshooting
or component replacement. It is not intended to show the physical routing of wires. When replacing a wire
or component, ensure the wire is routed in the same manner as the original factory wire.
IPGSM-DP-007-V2 [US Only]
TB 1
6
7
8
5
10
11
9
2
3
4
1
FOR EXTERNAL ANTENNA
50 OHM MMCX ONLY
PRIMARY POWER: 9 - 16.5 VAC
CURRENT: 900mA PEAK, 70mA STANDBY
BATTERY: 8V. 3.1 AHr FOR 24 Hr BACKUP
FCC:XXXXXXXXXX IC: YYYYYYYYYY
RSSI
M0
M1
GPRS
IBS
7720P PROGRAMMER PORT
NOT FOR TELEPHONE SERVICE USE!
RADIO
TROUBLE
LOW BATT
AC ON
LED Display
+12V In
FLT Out
ECP Out
ECP In
GND
TAMPER
SWITCH
RSSI/MODE
INDICATORS
MODE & STATUS
SWITCH
INTERNET
CONNECTIVITY
INDICATORS
iGSM Comm
Module
AC
ERTH GND
LOW
BATT
TROUBLE
ACTIVE
AC
PowerBoost1
DC+
DC-
OUT-
DC+
OUT+
N/U
DC-
OUT-
OUT+
RX
TX
GND
RED
WHT (LO BATT)
VIO
OUTPUT 1
OUTPUT 2
N/U
(RADIO TROUBLE)
1 5
ON
2
3
4
Buzzer
(Buzzer)
AC LOSS
(not used)
ANTENNA
GRN
YEL
STATUS
MESSAGE
FAULT
7720P
PROGRAMMER
PORT
RED
BLK
YEL
GRN
BLK
RED
CABINET
DOOR
FUSE
GRA
OPTIONAL CABINET
TAMPER SWITCH
BLK
+
BATTERY
BATTERY
7AH
CONDUIT
GRA
(AC ON)
To Facility Ground
(not supplied)
Use a Honeywell 712BNP,
Yuasa NP7-12, or equivalent.
To Router
To Fire Panel
To Fire Panel
YEL
Dialer Capture Module
Telco
1
ECP
Tip 2
Ring 2
ZN-
EOL
EOL
ZN+
PWR
GND
Tip 1
Ring 1
YEL
GRN
RED
BLK
Data Out
RED
GREEN
To Fire Panel Main Dialer
To Fire Panel Backup Dialer
Data in
GND
12V In
Telco
2
RED
BRN
WHT
VIO
BLK
WALL OUTLET
BOX (K14358)
TRANSFORMER
(N8167)
NOTES
All circuits are power limited except the backup battery which is non-power limited.
Non-power limited wiring must be separated from the power limited wiring by at least 1/4 inch.
If desired, use a Honeywell 955WH Tamper Switch with the 28-2 bracket.