Honeywell IPGSM-DP Smoke Alarm User Manual


 
IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide
11
RF Specifications
Band
Transmission
Frequency
(MHz)
Transmit
Power
(dBm)
Receive
Frequency
(MHz)
Receive
Sensitivity
(dBm)
Number
of
Channels
Channel
Spacing
(MHz)
Duplex
Separation
(kHz)
GSM 850
824-849 33 869-894 -107 124 200 45
GSM 900
890-915 33 935-960 -107 124 200 45
GSM 1800
1710-1785 30 1805-1880 -106 374 200 95
GSM 1900
1850-1910 30 1930-1990 -105.5 299 200 80
IPGSM-DP Specifications
ITEM SPECIFICATION
Cabinet Dimensions:
Width = 12 3/4 inches
Height = 14 7/8 inches
Depth = 3 inches
Transformer: N8167
Primary – 120VAC, 60Hz
Secondary – 18VAC, 50VA
Battery:
12V, 7Ah sealed lead acid type (not supplied)
Use a Honeywell 712BNP, Yuasa NP7-12 or equivalent.
Battery Charging Current:
maximum 1A
Supervision:
The AC power, backup battery, IP communications, and GSM
communications are monitored.