Honeywell 96d Thermostat User Manual


 
M-511401 96d User Manual 65
8/10 Honeywell
System Programming
Tests Menu
Test Sequence
When test sequence is selected from the main Tests menu, the
controller will display the Test sequence screen.
If Esc is pressed on the keypad, the main Tests menu screen will be
displayed. However, to perform system tests, press any key to proceed
to the first test screen.
This screen tests each component individually and will advance only to
the next component when a key is pressed. This option will display 13
screens. Screens 1, 2 and 3 test Relays, BUZZER and LEDs.
The following six screens prompt the user to press the keypad buttons,
in turn: left, right, up, down, Silence, Enter and Esc. The system will not
advance until a key is pressed.
Test sequence
Relays activated
Any key to continue
Esc to quit
Test sequence
BUZZER activated
Any key to continue
Esc to quit
Test sequence
Press ‘left’
Esc to quit