Heatiator NEVO4236I NEVO3630I Indoor Fireplace User Manual


 
Heatilator • Evolution • 4065-114 Rev. o • 11/11 45
CAULK
G. Install Metal Roof Flashing
See minimum vent heights for various pitched roofs
(Figure 10.14) to determine the length of pipe to extend
through the roof.
Slide the roof ashing over the pipe sections extending
through the roof as shown in Figure 10.15.
Horizontal
overhang
12
X
20 in.
(508 mm)
Lowest
Discharge
Opening
Termination
Cap
Roof Pitch
is X / 12
Vertical
wall
H (min.) - Minimum height
from roof to lowest
discharge opening.
24 in. min.
(610 mm)
Roof Pitch H (Min.) Ft. Roof Pitch H (Min.) Ft.
Flat to 6/12 1.0* Over 11/12 to 12/12 4.0
Over 6/12 to 7/12 1.25* Over 12/12 to 14/12 5.0
Over 7/12 to 8/12 1.5* Over 14/12 to 16/12 6.0
Over 8/12 to 9/12 2.0* Over 16/12 to 18/12 7.0
Over 9/12 to 10/12 2.5 Over 18/12 to 20/12 7.5
Over 10/12 to 11/12 3.25 Over 20/12 to 21/12 8.0
* 3 ft. minimum in snow regions
Storm Collar
Roof
Flashing
Figure 10.14 Minimum Height From Roof To Lowest Discharge
Opening
Figure 10.15
H. Assemble and Install Storm Collar
CAUTION! Risk of Cuts, Abrasions or Flying Debris.
Wear protective gloves and safety glasses during installa-
tion. Sheet metal edges are sharp.
Connect both halves of the storm collar with two screws
(see Figure 10.16).
Wrap the storm collar around the exposed pipe section
closest to the roof and align brackets. Insert a bolt
(provided) through the brackets and tighten the nut to
complete the storm collar assembly (Figure 10.17). Make
sure the collar is tight against the pipe section.
Slide the assembled storm collar down the pipe section
until it rests on the roof ashing.
Caulk around the top of the storm collar (see Figure
10.24).
Figure 10.16 Assembling the Storm Collar
Figure 10.17 Assembling the Storm Collar Around the Pipe
NOTICE: Failure to properly caulk the roof ashing and pipe
seams may permit entry of water.
• Caulk the gap between the roof ashing and the outside
diameter of the pipe.
• Caulk the perimeter of the ashing where it contacts the
roof surface. See Figure 10.15.
Caulk the overlap seam of any exposed pipe sections that
are located above the roof line.