Heatiator HEIR42T Indoor Fireplace User Manual


 
27
Heatilator •
HEIR36, HEIR42, HEIR50 • 2285-900 Rev. D • 8/12
H
1
V
1
1. Top Vent - Horizontal Termination
Figure 7.3
One Elbow
Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles between ceiling restops.
ALWAYS maintain speci ed clearances around venting and restop systems.
Install wall shield and ceiling restops as speci ed.
Failure to keep insulation or other material away from vent pipe may cause re.
WARNING
HEIR36 (NG/LP), HEIR42 (NG/LP),
HEIR50 (NG/LP)
V
1
Minimum H
1
Maximum
2 ft 610 mm 7 in* 178 mm
3 ft 914 mm 2 ft 610 mm
4 ft 1.2 m 4 ft 1.2 m
5 ft 1.5 m 9 ft 2.7 m
6 ft 1.8 m 12 ft 3.7 m
7 ft 2.1 m 14 ft 4.3 m
10 ft 3.0 m 20 ft 6.1 m
20 ft 6.1 m 40 ft 12.2 m
After V
1
= 6 ft then H
1
= 2 x V ft Maximum
V
1
+ H
1
= 60 ft Maximum
*when used with approved termination caps
Note: Flue restrictor is permit-
ted ONLY on 30 ft. minimum
vertical runs with no elbows.
WARNING! Risk of Fire!
• HEIR36(NG/LP), HEIR42(NG/LP) and HEIR50(NG/LP) models
require a minimum of 24 inches of vertical venting before attaching
any elbow to the appliance.
DO NOT attach elbow directly to the appliance.