Table 9. Charging Table for G24 Series (2 Ton)
2 TON MODELS
OUTDOOR TEMPERATURE (° F)
0 10 20 30 40 50 60
Suc.
Press
Liq.
Press.
Dis.
Temp.
Suc.
Press.
Liq.
Press.
Dis.
Temp.
Suc.
Press.
Liq.
Press.
Dis.
Temp.
Suc.
Press.
Liq.
Press.
Dis.
Temp.
Suc.
Press.
Liq.
Press.
Dis.
Temp.
Suc.
Press.
Liq.
Press.
Dis.
Temp.
Suc.
Press.
Liq.
Press.
Dis.
Temp.
35 198 77 50 227 92 64 256 107 79 284 122 94 307 136 111 347 150 127 387 165
36 205 75 51 233 90 65 260 105 80 288 120 95 314 133 112 354 146 128 394 158
37
212 73
52
239 88
66
265 103
81
292 118
96
321 130
113
361 141
129
401 152
38 219 71 53 245 86 67 270 101 82 295 116 97 328 128 114 368 137 130 408 146
39
226 69
54
250 84
68
275 99
83
299 114
98
335 125
115
375 132
131
415 140
40 233 67 55 256 82 69 279 97 84 303 112 99 342 122 116 382 128 132 422 134
41 240 65 56 262 80 70 284 95 85 306 110 100 349 119 117 389 123 133 429 128
Table 10. Charging Table for G30 Series (2.5 Ton)
2.5 TON MODELS
OUTDOOR TEMPERATURE (° F)
0 10 20 30 40 50 60
Suc.
Press
Liq.
Press.
Dis.
Temp.
Suc.
Press.
Liq.
Press.
Dis.
Temp.
Suc.
Press.
Liq.
Press.
Dis.
Temp.
Suc.
Press.
Liq.
Press.
Dis.
Temp.
Suc.
Press.
Liq.
Press.
Dis.
Temp.
Suc.
Press.
Liq.
Press.
Dis.
Temp.
Suc.
Press.
Liq.
Press.
Dis.
Temp.
34 195 82 49 223 98 64 252 114 79 280 130 93 295 145 107 318 159 121 341 173
35 202 80 50 229 96 65 257 112 80 284 128 94 302 143 108 325 155 122 348 167
36
209 78
51
235 94
66
261 110
81
288 126
95
309 140
109
332 150
123
355 161
37 216 76 52 241 92 67 266 108 82 291 124 96 316 137 110 339 146 124 362 154
38
223 74
53
247 90
68
271 106
83
295 122
97
323 134
111
346 141
125
369 148
39 230 72 54 253 88 69 276 104 84 299 120 98 330 131 112 353 137 126 376 142
40 237 70 55 259 86 70 280 102 85 302 118 99 337 128 113 360 132 127 383 136
REFRIGERANT CHARGING TABLES - HEATING MODE
Shaded boxes indicate flooded conditions.
Rated design values are based on 70 °F indoor air temperature .
1. All pressures are listed psig and all temperatures in °F
2. Discharge temperatures greater than values listed indicate an undercharged system.
3. Charging tables should only be used as a guide.
4. Unit charge must be verified in cooling season.