Heat Controller HTH Heat Pump User Manual


 
41
Installation, Operation & Maintenance HTV/HTD/HTH SERIES Heat Controller, Inc.
Performance Data — HT 070 - Full Load
1950 CFM Nominal (Rated) Air ow Cooling, 2100 CFM Nominal (Rated) Air ow Heating Performance capacities shown in thousands of Btuh
EWT
°F
Cooling - EAT 80/67°F Heating - EAT 70°F
GPM
WPD
CFM
TC SC kW
EER HR LWT HWC
GPM
WPD
CFM
HC kW
COP
HE
LAT LWT HWC
PSI
FT
PSI
FT
20
Operation not recommended
17.0 8.9 20.6 1750 46.6 4.66 2.9 30.7 94.7 16.4 5.2
17.0 8.9 20.6 2050 47.3 4.52 3.1 31.9 91.4 3.8 5.0
30
8.5 2.2 5.1 1590 82.4 50.1 3.04 27.1 92.8 22.2 3.6 8.5 2.2 5.1 1750 51.6 4.77 3.2 35.3 97.3 21.7 5.4
8.5 2.2 5.1 1850 83.8 53.9 3.15 26.6 94.6 22.2 3.7 8.5 2.2 5.1 2050 52.4 4.63 3.3 36.6 93.7 8.6 5.2
12.8 4.6 10.6 1590 82.3 50.0 2.90 28.4 92.2 14.7 3.6 12.8 4.6 10.6 1750 54.0 4.83 3.3 37.5 98.6 24.1 5.5
12.8 4.6 10.6 1850 83.7 53.8 3.00 27.9 93.9 14.7 3.7 12.8 4.6 10.6 2050 54.8 4.68 3.4 38.8 94.8 6.1 5.4
17.0 7.6 17.6 1590 81.9 49.8 2.84 28.9 91.6 11.0 3.6 17.0 7.6 17.6 1750 55.3 4.86 3.3 38.7 99.2 25.4 5.6
17.0 7.6 17.6 1850 83.3 53.5 2.94 28.3 93.3 11.0 3.7 17.0 7.6 17.6 2050 56.1 4.71 3.5 40.1 95.3 4.7 5.5
40
8.5 1.6 3.8 1590 81.3 49.8 3.27 24.9 92.4 22.2 3.9 8.5 1.6 3.8 1750 59.4 4.96 3.5 42.4 101.4 30.0 5.9
8.5 1.6 3.8 1850 82.7 53.5 3.39 24.4 94.3 22.2 4.0 8.5 1.6 3.8 2050 60.3 4.80 3.7 43.9 97.2 10.3 5.7
12.8 3.9 8.9 1590 82.2 50.1 3.09 26.6 92.8 14.8 3.6 12.8 3.9 8.9 1750 62.1 5.02 3.6 45.0 102.9 32.9 6.1
12.8 3.9 8.9 1850 83.6 53.9 3.21 26.1 94.6 14.8 3.7 12.8 3.9 8.9 2050 63.1 4.87 3.8 46.5 98.5 7.3 5.9
17.0 6.7 15.5 1590 82.4 50.1 3.02 27.3 92.7 11.1 3.6 17.0 6.7 15.5 1750 63.6 5.06 3.7 46.4 103.7 34.5 6.2
17.0 6.7 15.5 1850 83.8 53.9 3.13 26.8 94.5 11.1 3.7 17.0 6.7 15.5 2050 64.6 4.90 3.9 47.9 99.2 5.6 6.1
50
8.5 1.3 3.0 1590 79.1 49.0 3.54 22.3 91.2 21.9 4.5 8.5 1.3 3.0 1750 66.9 5.14 3.8 49.4 105.4 38.4 6.5
8.5 1.3 3.0 1850 80.5 52.6 3.67 21.9 93.0 21.9 4.6 8.5 1.3 3.0 2050 67.9 4.99 4.0 50.9 100.7 12.0 6.3
12.8 3.4 7.8 1590 80.8 49.6 3.34 24.2 92.2 14.7 4.0 12.8 3.4 7.8 1750 70.1 5.23 3.9 52.3 107.1 41.8 6.8
12.8 3.4 7.8 1850 82.2 53.3 3.46 23.8 94.0 14.7 4.1 12.8 3.4 7.8 2050 71.2 5.07 4.1 53.9 102.1 8.5 6.6
17.0 6.0 13.9 1590 81.5 49.8 3.24 25.1 92.5 11.1 3.8 17.0 6.0 13.9 1750 71.8 5.27 4.0 53.8 108.0 43.7 7.0
17.0 6.0 13.9 1850 82.9 53.6 3.36 24.7 94.3 11.1 3.9 17.0 6.0 13.9 2050 72.9 5.11 4.2 55.5 102.9 6.5 6.8
60
8.5 1.2 2.7 1590 76.1 47.8 3.87 19.6 89.3 21.4 5.4 8.5 1.2 2.7 1750 74.4 5.34 4.1 56.2 109.4 46.8 7.3
8.5 1.2 2.7 1850 77.4 51.4 4.01 19.3 91.1 21.4 5.6 8.5 1.2 2.7 2050 75.5 5.18 4.3 57.9 104.1 13.6 7.1
12.8 3.1 7.1 1590 78.3 48.7 3.63 21.6 90.7 14.5 4.7 12.8 3.1 7.1 1750 78.0 5.44 4.2 59.4 111.3 50.7 7.7
12.8 3.1 7.1 1850 79.7 52.3 3.76 21.2 92.5 14.5 4.8 12.8 3.1 7.1 2050 79.2 5.28 4.4 61.2 105.8 9.6 7.4
17.0 5.6 13.0 1590 79.3 49.1 3.52 22.6 91.3 11.0 4.4 17.0 5.6 13.0 1750 80.0 5.50 4.3 61.2 112.3 52.8 7.9
17.0 5.6 13.0 1850 80.7 52.7 3.64 22.2 93.1 11.0 4.5 17.0 5.6 13.0 2050 81.2 5.33 4.5 63.0 106.7 7.4 7.7
70
8.5 1.1 2.6 1590 72.4 46.3 4.26 17.0 87.0 20.9 6.7 8.5 1.1 2.6 1750 81.9 5.56 4.3 62.9 113.3 55.2 8.1
8.5 1.1 2.6 1850 73.7 49.8 4.42 16.7 88.7 20.9 6.8 8.5 1.1 2.6 2050 83.2 5.38 4.5 64.8 107.6 15.2 7.9
12.8 3.0 6.8 1590 75.0 47.4 3.98 18.9 88.6 14.2 5.8 12.8 3.0 6.8 1750 86.0 5.68 4.4 66.6 115.5 59.6 8.6
12.8 3.0 6.8 1850 76.3 50.9 4.12 18.5 90.4 14.2 5.9 12.8 3.0 6.8 2050 87.3 5.50 4.6 68.5 109.4 10.7 8.4
17.0 5.4 12.4 1590 76.3 47.9 3.85 19.8 89.4 10.7 5.4 17.0 5.4 12.4 1750 88.2 5.75 4.5 68.6 116.7 61.9 8.9
17.0 5.4 12.4 1850 77.6 51.5 3.99 19.5 91.2 10.7 5.5 17.0 5.4 12.4 2050 89.5 5.57 4.7 70.5 110.4 8.3 8.7
80
8.5 1.2 2.7 1590 68.4 44.7 4.72 14.5 84.5 20.3 8.2 8.5 1.2 2.7 1750 89.5 5.79 4.5 69.8 117.4 63.6 9.1
8.5 1.2 2.7 1850 69.5 48.1 4.89 14.2 86.2 20.3 8.4 8.5 1.2 2.7 2050 90.9 5.61 4.7 71.7 111.0 16.9 8.8
12.8 2.9 6.7 1590 71.2 45.8 4.40 16.2 86.2 13.8 7.1 12.8 2.9 6.7 1750 94.1 5.93 4.6 73.9 119.8 68.4 9.8
12.8 2.9 6.7 1850 72.4 49.3 4.56 15.9 88.0 13.8 7.3 12.8 2.9 6.7 2050 95.5 5.75 4.9 75.9 113.2 11.9 9.5
17.0 5.2 12.1 1590 72.6 46.4 4.24 17.1 87.1 10.5 6.6 17.0 5.2 12.1 1750 96.7 6.02 4.7 76.1 121.1 71.0 10.1
17.0 5.2 12.1 1850 73.8 49.9 4.40 16.8 88.8 10.5 6.7 17.0 5.2 12.1 2050 98.1 5.83 4.9 78.2 114.3 9.2 9.8
90
8.5 1.2 2.8 1590 64.1 43.0 5.26 12.2 82.0 19.7 10.0 8.5 1.2 2.8 1750 97.3 6.04 4.7 76.7 121.5 72.0 10.2
8.5 1.2 2.8 1850 68.1 47.4 5.07 13.4 85.4 19.7 9.0 8.5 1.2 2.8 2050 98.8 5.85 4.9 78.8 114.6 18.5 9.9
12.8 2.9 6.7 1590 67.0 44.1 4.89 13.7 83.6 13.4 8.8 12.8 2.9 6.7 1750 102.6 6.22 4.8 81.3 124.3 77.2 11.0
12.8 2.9 6.7 1850 68.1 47.4 5.07 13.4 85.4 13.4 9.0 12.8 2.9 6.7 2050 104.1 6.03 5.1 83.6 117.0 13.1 10.7
17.0 5.2 12.0 1590 68.4 44.7 4.71 14.5 84.5 10.1 8.2 17.0 5.2 12.0 1750 105.5 6.32 4.9 83.9 125.8 80.1 11.4
17.0 5.2 12.0 1850 69.6 48.1 4.88 14.2 86.3 10.1 8.4 17.0 5.2 12.0 2050 107.1 6.12 5.1 86.2 118.4 10.1 11.1
100
8.5 1.2 2.8 1590 59.8 41.2 5.88 10.2 79.9 19.2 12.2
Operation not recommended
8.5 1.2 2.8 1850 60.9 44.3 6.09 10.0 81.6 19.2 12.5
12.8 2.9 6.7 1590 62.6 42.3 5.46 11.5 81.2 13.0 10.8
12.8 2.9 6.7 1850 63.7 45.5 5.66 11.2 83.0 13.0 11.0
17.0 5.2 12.0 1590 64.0 42.9 5.27 12.2 82.0 9.9 10.1
17.0 5.2 12.0 1850 65.1 46.2 5.46 11.9 83.8 9.9 10.3
110
8.5 1.1 2.6 1590 55.7 39.5 6.61 8.4 78.2 18.8 14.7
8.5 1.1 2.6 1850 56.7 42.5 6.85 8.3 80.0 18.8 15.0
12.8 2.9 6.6 1590 58.3 40.6 6.13 9.5 79.2 12.7 13.1
12.8 2.9 6.6 1850 59.3 43.6 6.36 9.3 81.0 12.7 13.4
17.0 5.1 11.8 1590 59.6 41.1 5.91 10.1 79.8 9.6 12.3
17.0 5.1 11.8 1850 60.7 44.2 6.12 9.9 81.6 9.6 12.6
120
8.5 0.9 2.1 1590 52.0 38.1 7.45 7.0 77.4 18.6 17.6
8.5 0.9 2.1 1850 52.9 41.0 7.72 6.8 79.2 18.6 18.0
12.8 2.7 6.2 1590 54.2 39.0 6.91 7.8 77.8 12.5 15.8
12.8 2.7 6.2 1850 55.2 41.9 7.16 7.7 79.6 12.5 16.1
17.0 5.0 11.5 1590 55.5 39.4 6.65 8.3 78.2 9.4 14.9
17.0 5.0 11.5 1850 56.4 42.4 6.90 8.2 80.0 9.4 15.2
Interpolation is permissible; extrapolation is not. Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
AHRI/ISO certied conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating. See performance correction tables for operating conditions other than those listed above.
Table does not reect fan or pump power corrections for AHRI/ISO conditions. For operation in the shaded areas, please see the Performance Data Selection Notes.
All performance is based upon the lower voltage of dual voltage rated units.