Heat Controller HMG**X1E Air Conditioner User Manual


 
30
CONTROL SIGNAL & MODE OPERATION TOTAL KW BOARD ACTION
W1 & W2
EHEAT
ON
5 KW
Stage 1 Heat on instantly
Heat blower on after 3 second delay
10 KW
Stage 1 Heat on instantly
Heat blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
15 KW
Stage 1 Heat on instantly
Heat blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 10 seconds delay
20 KW
Stage 1 Heat on instantly
Heat blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 10 seconds delay
Stage 4 Heat on after 15 seconds delay
25 KW
Stage 1 Heat on instantly
Heat blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 10 seconds delay
Stage 4 Heat on after 15 seconds delay
Stage 5 Heat on after 20 seconds delay
30 KW
Stage 1Heat on instantly
Heat blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 10 seconds delay
Stage 4 Heat on after 15 seconds delay
Stage 5 Heat on after 20 seconds delay
Stage 6 Heat on after 25 seconds delay
OFF
Heat stages off instantly
Blower off after 15 second delay
W1 & Y/Y2
AUX HEAT
ON
5 KW
Stage 1 Heat on instantly
Cool blower on after 3 second delay
10 KW
Stage 1 Heat on instantly
Cool blower on after 3 second delay
15 KW
Stage 1 Heat on instantly
Cool blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
20 KW
Stage 1 Heat on instantly
Cool blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 10 seconds delay
25 KW
Stage 1 Heat on instantly
Cool blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 10 seconds delay
30 KW
Stage 1 Heat on instantly
Cool blower on after 3 second delay
Stage 2 Heat on after 5 seconds delay
Stage 3 Heat on after 10 seconds delay
Stage 4 Heat on after 15 seconds delay
OFF
Heat stages off instantly
Heat blower turns off after 40 second delay
Table 12. Control Board Operation - Continued