FLOOR PROTECTION
The floor must be non-combustible material, extending beneath heater and to the front/sides/rear as indicated. The floor must be
non-combustible or otherwise adequately protected from radiant heat given off by the unit and from sparks and falling embers. A
layer of thin brick or ceramic tile over a combustible floor is not sufficient.
In USA installations, it is necessary to install a non-combustible floor protector at least 16 inches in front and 8 inches to both
sides of the fuel loading doors. See *exception below.
In Canada, similar floor protection must be provided 18 inches (450mm) in front and 8 inches (200mm) from the sides and rear of
the stove. See *exception below.
*EXCEPTION: Non-combustible floor protections must extend beneath the flue pipe when installed with horizontal venting and
extend 2 inches (51mm) beyond each side.
Minimum 16"
(406mm) from
fuel loading
door
8"(200mm)
USA
44-1/2"(1130mm) Minimum
36-3/4"
(932mm)
Minimum
Fuel loading doors
Front
Side
8"
(200mm)
Minimum 450mm
(18") from each
fuel loading door
CANADA
1187mm
(46-3/4")
Minimum
Fuel loading doors
Front
Side
200mm (8")
1264mm (49-3/4") Minimum
200mm
(8")
CANADA
200mm (8")
200mm
(8")
450mm (18")
1187mm
(46-3/4")
Minimum
1010mm (39-3/4")
Minimum
200mm
(8")
SIDE FUEL DOOR LOCKED SHUT
BOTH FUEL DOORS ACCESSIBLE
DRAWINGS ARE FOR ILLUSTRATION PURPOSES ONLY AND ARE NOT TO SCALE.
16" (406mm) from fuel
loading door
8"
(200mm)
USA
Front Fuel
loading door
33"(838mm) Minimum
36-3/4"
(933mm)
Minimum
10-1/2"
(267mm)
Minimum Hearth Requirements ONLY