13
P68 Pellet Stove
#8 Installing through the ceiling
Through the ceiling vent, follow PLvent
manufacturers recommendations when using wall
and ceiling pass through. Note: Do not place joints
within wall pass-throughs.
Fig. 14
PL vent manufacturer's
firestop spacer and
support
(See Page 5 for
corner installation
clearances)
Minimum flue vent
configuration
It is recommended that outside
air be installed with this venting
configuration to reduce smoke
and creosote smell in the room
in the event of power failure.
Min. above ground level
18"
Storm collar
Flashing
3" min.
3" min.
12" min.
3" min.
Venting
Fig. 15
3" min.
No insulation or
other combustible
materials are
allowed within 3" of
the PL vent pipe.
12" min. wall to outlet
36" min clearance to any
combustible material
Fig. 16