Goodmans GPC1324H41A Air Conditioner User Manual


 
17
COOLING PERFORMANCE DATA GPC1330H41AA
MODEL: GPC1330H41A*
EXPANDED PERFORMANCE DATA
COOLING OPERATION
Design Subcooling, 12±3 °F @ the liquid access fitting connection AHRI 95 test conditions. Design Superheat 8±3 °F @ the compressor suction access fitting connection.
Outdoor Ambient Temperature
65 75 85 95 105 115
Entering Indoor Wet Bulb Temperature
IDB*Airflow 59636771596367715963677159 63 67 715963677159636771
MBh 29.2 29.8 31.9 34.1 28.5 29.2 31.1 33.3 27.9 28.5 30.4 32.5 27.2 27.8 29.7 31.7 25.8 26.4 28.2 30.1 23.9 24.4 26.1 27.9
S/T 1.00 0.92 0.75 0.56 1.00 0.96 0.78 0.58 1.00 1.00 0.80 0.60 1.00 1.00 0.83 0.62 1.00 1.00 0.86 0.64 1.00 1.00 0.86 0.65
Delta T23211915222219152222191521 22 19 152021191519191814
1180 KW 2.10 2.14 2.21 2.27 2.25 2.30 2.37 2.44 2.39 2.44 2.51 2.59 2.50 2.56 2.64 2.72 2.60 2.66 2.74 2.83 2.69 2.75 2.84 2.93
AMPS 8.9 9.1 9.3 9.6 9.5 9.7 10.0 10.3 10.2 10.4 10.7 11.0 10.8 11.0 11.3 11.7 11.4 11.6 12.0 12.3 12.0 12.2 12.6 13.0
HI PR 236 254 269 280 265 285 301 314 302 324 343 357 343 370 390 407 386 416 439 458 427 459 485 506
LO PR 114 121 132 140 120 128 139 148 125 133 145 154 131 139 152 162 137 146 159 170 142 151 165 176
MBh 28.4 29.0 31.0 33.1 27.7 28.3 30.2 32.3 27.0 27.6 29.5 31.6 26.4 27.0
28.8
30.8 25.1 25.6 27.4 29.2 23.2 23.7 25.3 27.1
S/T 0.94 0.88 0.72 0.54 0.97 0.91 0.74 0.56 1.00 0.94 0.76 0.57 1.00 0.97
0.79
0.59 1.00 1.00 0.82 0.61 1.00 1.00 0.82 0.62
Delta T23221916242320162423201623 23
20
16 22 22 20 16 20 21 18 15
80 1050 KW 2.08 2.13 2.19 2.25 2.23 2.28 2.35 2.42 2.37 2.42 2.49 2.57 2.48 2.54
2.62
2.70 2.58 2.64 2.72 2.81 2.67 2.73 2.81 2.91
AMPS 8.9 9.0 9.3 9.6 9.4 9.6 9.9 10.2 10.1 10.3 10.6 11.0 10.7 10.9
11.2
11.6 11.3 11.5 11.9 12.3 11.9 12.1 12.5 12.9
HI PR 234 252 266 277 263 282 298 311 299 321 339 354 340 366
386
403 383 412 435 453 423 455 480 501
LO PR 112 120 131 139 119 126 138 147 123 131 143 153 130 138
151
160 136 145 158 168 141 150 163 174
MBh 26.2 26.7 28.6 30.5 25.6 26.1 27.9 29.8 25.0 25.5 27.2 29.1 24.3 24.9 26.6 28.4 23.1 23.6 25.3 27.0 21.4 21.9 23.4 25.0
S/T 0.91 0.85 0.69 0.52 0.94 0.88 0.72 0.54 0.96 0.90 0.74 0.55 0.99 0.93 0.76 0.57 1.03 0.97 0.79 0.59 1.04 0.98 0.79 0.59
Delta T24232016242320162423201624 23 20 162423201622211915
920 KW 2.04 2.08 2.14 2.20 2.18 2.23 2.29 2.37 2.31 2.36 2.43 2.51 2.43 2.48 2.55 2.63 2.52 2.58 2.66 2.74 2.61 2.66 2.75 2.83
AMPS 8.7 8.8 9.1 9.3 9.2 9.4 9.7 10.0 9.9 10.1 10.4 10.7 10.5 10.7 11.0 11.3 11.0 11.3 11.6 12.0 11.6 11.8 12.2 12.6
HI PR 227 244 258 269 255 274 289 302 290 312 329 343 330 355 375 391 371 399 422 440 410 441 466 486
LO PR 109 116 127 135 115 123 134 143 120 127 139 148 126 134 146 156 132 140 153 163 136 145 158 169
NOTE: Shaded area reflects ARI rating conditions
MBh 29.7 30.3 31.7 33.9 29.0 29.6 31.0 33.1 28.3 28.9 30.3 32.3 27.6 28.2 29.5 31.5 26.3 26.8 28.0 29.9 24.3 24.8 26.0 27.7
S/T 1.00 1.00 0.90 0.73 1.00 1.00 0.93 0.76 1.00 1.00 0.96 0.78 1.00 1.00 0.99 0.80 1.00 1.00 1.00 0.83 1.00 1.00 1.00 0.84
Delta T23242219232323192223232022 22 23 202021221919192018
1180 KW 2.12 2.16 2.22 2.29 2.27 2.32 2.39 2.46 2.40 2.45 2.53 2.61 2.52 2.58 2.66 2.74 2.63 2.68 2.77 2.86 2.71 2.77 2.86 2.95
AMPS 9.0 9.2 9.4 9.7 9.6 9.8 10.1 10.4 10.3 10.5 10.8 11.1 10.9 11.1 11.4 11.8 11.5 11.7 12.1 12.4 12.1 12.3 12.7 13.1
HI PR 239 257 271 283 268 288 304 317 305 328 346 361 347 373 394 411 390 420 443 463 431 464 490 511
LO PR 115 122 133 142 121 129 141 150 126 134 146 156 132 141 154 164 139 147 161 171 143 153 167 177
MBh 28.9 29.4 30.8 32.9 28.2 28.7 30.1 32.1 27.5 28.0 29.4 31.3 26.8 27.4 28.7 30.6 25.5 26.0 27.2 29.0 23.6 24.1 25.2 26.9
S/T 0.99 0.95 0.86 0.70 1.00 0.99 0.89 0.72 1.00 1.00 0.91 0.74 1.00 1.00 0.94 0.76 1.00 1.00 0.98 0.79 1.00 1.00 0.99 0.80
Delta T25242320252523202425232024 24 24 202223232021212219
85 1050 KW 2.10 2.14 2.21 2.27 2.25 2.30 2.37 2.44 2.39 2.44 2.51 2.59 2.50 2.56 2.64 2.72 2.60 2.66 2.74 2.83 2.69 2.75 2.84 2.93
AMPS 8.9 9.1 9.3 9.6 9.5 9.7 10.0 10.3 10.2 10.4 10.7 11.0 10.8 11.0 11.3 11.7 11.4 11.6 12.0 12.3 12.0 12.2 12.6 13.0
HI PR 236 254 269 280 265 285 301 314 302 324 343 357 343 370 390 407 386 416 439 458 427 459 485 506
LO PR 114 121 132 140 120 128 139 148 125 133 145 154 131 139 152 162 137 146 159 170 142 151 165 176
MBh 26.6 27.1 28.4 30.3 26.0 26.5 27.8 29.6 25.4 25.9 27.1 28.9 24.8 25.3 26.4 28.2 23.5 24.0 25.1 26.8 21.8 22.2 23.3 24.8
S/T 0.95 0.92 0.83 0.67 0.98 0.95 0.86 0.70 1.00 0.97 0.88 0.71 1.00 1.00 0.91 0.74 1.00 1.00 0.94 0.76 1.00 1.00 0.95 0.77
Delta T25252420262524212525242125 25 24 212424242022222219
920 KW 2.05 2.09 2.15 2.22 2.20 2.24 2.31 2.38 2.33 2.38 2.45 2.53 2.44 2.50 2.57 2.66 2.54 2.60 2.68 2.76 2.63 2.68 2.77 2.86
AMPS 8.7 8.9 9.1 9.4 9.3 9.5 9.7 10.1 10.0 10.2 10.5 10.8 10.5 10.8 11.1 11.4 11.1 11.3 11.7 12.0 11.7 11.9 12.3 12.7
HI PR 229 247 260 272 257 277 292 305 292 315 332 347 333 358 379 395 375 403 426 444 414 446 471 491
LO PR 110 117 128 136 116 124 135 144 121 129 140 150 127 135 148 157 133 142 155 165 138 147 160 170
* NOTE: Shaded area is AHRI Rating Conditions IDB: Entering Indoor Dry Bulb Temperature KW = Total system power
High and low pressures are measured at the liquid and suction access fittings. AMPS: Unit amps (comp.+ evaporator + condenser fan motors)