Friedrich PTAC - R410A Air Conditioner User Manual


 
6
Digital Packaged Terminal Air Conditioners & Heat Pumps
All units shall be factory assembled, piped, wired and fully charged with
310 for air conditioners and ARI standard 380 for heat pumps. Units
shall be UL listed and carry a UL label. All units shall be factory run-
tested to check operation and be Friedrich or equivalent.
The basic unit shall not exceed 16” high x 42” wide. Overall depth
of the unit from the rear of the Friedrich wall sleeve to the front of
the decorative front cover shall not exceed 21 ¼”. The unit shall be
designed so that room int
rusion may be as little as 7 ½”. Installations
in walls deeper than 13 ¼” may be accomplished with the use of a
deep wall sleeve (PDXWSEXT). Unit shall draw in ambient air through
both sides of an outdoor architectural louver or grille measuring 42”
.revuol eht fo noitrop elddim tuo ria tsuahxe llahs dna hgih 61 x ediw
The architectural louver and wall sleeve shall be designed so that the
louver may be installed f
rom the inside of the building.
REFRIGERATION SYSTEM – The refrigeration system shall be her-
metically sealed and consist of a rotary compressor that is externally
mounted on vibration isolators no smaller than 1 3/8” dia. x 1 ½” high;
condenser and evaporator coils constructed of copper tubes and
.etasnednoc fo snollag ½ 1 gniniater fo elbapac nap niard a evah dna
A tertiary condensate removal system shall also be incorporated for
of the building as a safeguard against damage to the interior room.
INDOOR AIR HANDLING SECTION – The indoor air handling sec-
tion shall consist of a tangential blower wheel direct driven by a totally
enclosed motor. The air handling system shall be designed to minimize
fan must have three fan speeds that may be selected by the user.
throughout the room. The grille shall be reversible to allow a change
personal injury or damage to the unit.
and reusable by cleaning with water or by vacuuming.
The chassis shall have a built-in damper capable of providing at least
damper closed to ensure a proper seal.
OUTDOOR AIR HANDLING SECTION – The outdoor air section
shall consist of a single injection molded fan shroud that incorporates
the outdoor motor mount into a single piece for ease of service and
assembly. The outdoor motor shall be totally enclosed, ball-bearing,
permanently lubricated and directly drive the outdoor fan/slinger ring.
CONTROLS – Covered controls shall be accessible in a compartment
at least 7½” wide with the controls no deeper than 1 ¼” in the opening
to facilitate easy operation of the unit.
The unit controls shall feature a soft blue LED readout that can display
either room temperature or setpoint temperature. The unit shall re-
ceive input from the digital control panel through push buttons labeled:
‘Cool’, ‘Heat’, ‘High Fan’, ‘Med Fan’, ‘Low Fan’,
’, ‘’ and ‘Power’.
When ‘Off’, the unit may be put directly into cooling or heating mode
by pressing the ‘Cool’ or ‘Heat’ button.
The unit must have the following energy saving and convenience
features built-in:
Quiet start/stop fan delay
Fan cycle control for cooling and heating independently
Room freeze protection
Random compressor restart
Electronic temperature limiting
The PTAC must also offer the ability to be controlled by a remote wall-
mounted thermostat wit
hout additional accessories. Low voltage inputs
will include: C (common), R (24V power), Y (cooling), GL (fan low), GH
(fan high), W (heat) and O (reversing valve on PDH heat pumps only).
PTAC models shall use a single stage cool / single stage heat ther-
mostat. PTHP models shall use a single stage cool / two-stage heat
thermostat. An accessory thermostat must be available from the
manufacturer, RT6 or equivalent. The RT6
thermostat will provide
.sedom naf dna taeh ,looc morf noitceles edom ,tnioptes erutarepmet
The thermostat must also allow the selection of fan speed between
high and low speed.
Other controls accessible without removal of the chassis shall include
fan cycle switch, fresh air vent control and emergency heat override
switch (heat pump only).
ELECTRICAL CONNECTION – All PTAC/PTHP units shall come from
the factory with a power cord installed. All 230/208V power cords shall
feature a leakage current detection device on the plug head. All units
shall feature a 6-pin connector for removal of the power cord. The
power cord shall be interchangeable to allow changes to the heater
output based on the property/electrical requirements.
GENERAL CONSTRUCTION – The wall sleeve shall be constructed
of 18-gauge Galvanized zinc-coated steel. It shall be prepared by
a process where it is zinc phosphate pretreated and sealed with a
cured for durability. The sleeve shall be shipped with a protective
weatherboard and a structural center support, and be insulated for
shipped separately and made from stamped or extruded anodized
aluminum. All louvers shall be in the horizontal plane.
clips. As an option the cover may be attached by two screws to pre-
vent tampering. The front panel will feature a contoured discharge
with no sharp corners.
CORROSION PROTECTION – The unit shall have corrosion-resistant
fans, fan shroud and drain pan for corrosion protection and to prevent
rust on the side of the building below the outdoor louver. The unit shall
-
rioration. The outdoor coil shall have Diamonblue corrosion protection
applications including seacoast environments. All outdoor coils shall
also have stainless steel endplates to eliminate rusting of the endplates.
WARRANTY – The warranty is one year on all parts and 5 years on
the sealed system including compressor, indoor and outdoor coils and
refrigerant tubing.
Cooling: 7600 – 15,000 Btuh
Heating: 7600 – 14500 Btuh (Heat Pump)
6824 – 17060 Btuh (Electric Heat)
Friedrich Models: PDE – Coo
ling with or without electric heat
PDH – Heat Pump with electric heat