Enviro EG 28 Indoor Fireplace User Manual


 
DECIDING WHERE TO LOCATE YOUR STOVE
DIMENSIONS:
FIG. 1
Front Width: 22"/ 56 cm
Rear Width: 22"/ 56 cm
Height: 27-1/2"/ 70 cm*
Depth 19"/ 48 cm
(*not including vent coupling)
Shipping Weight: 210 lbs/95 kg
CLEARANCES:
A. Side wall to stove 10"/ 25 cm
B. Rear wall to stove 4"/ 10 cm
C. Combustible to stove Top 22”/ 56 cm
D. Floor to stove 0"/ 0 cm
E. Corner clearance 2"/ 5 cm
F. Alcove depth 48"/ 122 cm
Maintain sufficient clearances
for service and maintenance
FIG. 2
The stove should be located out of traffic and away from furniture and draperies.
The stove should have sufficient access for its safe operation and maintenance.
Locate a position where the flue system of the stove can be properly installed without damaging the integrity
of the building. e.g. cutting a wall or ceiling joist.
The stove can be installed on any standard flooring materials i.e. Wood, carpet or linoleum.
Check stove and flue system clearance requirements.
Locate the stove where it can be accessed by a gas supply line.
Locate the stove in a large and open room that is centrally located in the house. This will optimize heat
circulation and comfort.
As the stove is equipped with a convection fan, ensure that an electrical outlet is within 6ft. (1.8m) of the
stove.
These stoves can be installed in bedrooms.
(IN CANADA: must be installed with a listed wall thermostat)
(IN USA: see current ANSI Z223.1 for installation instructions.)
The
flow of combustion and ventilation air must not be obstructed.
4