Empire Comfort Systems FAW-40-1IP Furnace User Manual


 
12427-2-0903
Page 10
SERVICE AND MAINTENANCE SUGGESTIONS
CALL SERVICEMAN
GENERAL: All furnaces have been fire-tested to check for proper
operation. This includes, main burner flame, pilot flame, fan operation,
fan control, limit control and automatic valve operation. If the furnace
fails to function on initial installation, it is advisable to re-check the
following:
1. 115 volts to the junction box.
2. Inlet gas pressure.
3. The 24 volt system.
4. Type of gas being used and that shown on the rating label.
The Service Department at Empire Comfort Systems, Inc. may be
contacted to assist in servicing furnace.
Standing Pilot Model
Servicing the Pilot and Main Burners, Pilot Orifice, Thermocouple,
and Main Burner Orifices: Disconnect the gas supply at the inlet to the
control valve. Then remove the burner door to gain access to the above
listed components.
Spark Igniter Does Not Light Pilot: With air in the gas line, such as
when the furnace is first installed or was off all summer, the pilot flame
may be too lean to ignite on the first few trials. Turn the control valve
knob to pilot position and depress the red reset button. Holding the
button down continually to bleed the line;.
1. Use lighter rod to light pilot with a match.
2. Use the piezo ignitor at 30 second intervals until it lights.
If Electrode Does Not Produce Spark:
1. Check wire connections.
2. Check gap for pilot burner to the electrode tip. Should be between
1/8" (3mm) and 3/16" (5mm). Electrode wire and tip must be more
than 1/4" (6mm) away from all other metal components.
If Pilot Does Not Light By Any Means:
1. Check valve knob for being in the "Pilot" position.
2. Check pilot adjustment for being full open (counterclockwise to
open).
3. If gas is available in the supply tubing, the pilot orifice and/or pilot
burner is probably restricted by a spider web. Clean pilot assembly
and relight.
If Pilot Does Not Remain On After Releasing Knob:
1. Follow instructions and hold button down longer and harder.
2. Determine if pilot flame extends past thermocouple; if not, adjust
input or clean pilot burner.
3. Replace thermocouple if millivolts read less than 15 millivolts.
Main Gas Valve Does Not Open When Thermostat Is Turned To On:
1. Check for 24 volts to valve by removing one wire and touching to
the SAME TERMINAL it was on. Terminal should have a light
spark. DO NOT SHORT ACROSS TERMINALS, AS IT WILL
BURN OUT THE WALL THERMOSTAT.
2. Thermostat wires at the wall may be shorted, so check for a faulty
thermostat.
3. To check for line voltage to furnace, remove front panel and short
across two-terminal fan control to allow fan to operate (Figure 14).
CAUTION: Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous operation.
Verify proper operation after servicing.
IP-Model Pilot
This heater is using a Honeywell "Smart Valve" system for intermittent
pilot ignition.
On a call for heat by the thermostat this control turns on a 24 volt mini
hot surface ignitor which lights a pilot that in turn lights the main burner.
The gas valve used in this system is a step opening which opens at a
lower pressure for ignition and then steps to a full inlet pressure of 4"
H
2
O pressure on Natural gas and 10" H
2
0 pressure on LP gas.
Pilot Flame Adjustment
The pilot flame should envelop 3/8 to 1/2 inch (10 to 13mm) of the tip
of the flame rod. See Figure 10.
To adjust:
1. Remove the pilot adjustment cover screw.
2. Turn the inner adjustment screw clockwise
to decrease
or counterclockwise
to increase pilot flame. Pilot adjust-
ment is shipped at full flow rate. Turn the inner adjustment screw
clockwise
if the inlet pressure is too high.
3. Replace the cover screw after the adjustment to prevent gas
leakage.
ON
OFF
IGNITOR
CONTROL
INLET PRESSURE TAP
OUTLET PRESSURE TAP
PILOT ADJUSTMENT-
UNDER CAP SCREW
PILOT OUTLET
PRESSURE REGULATOR
ADJUSTMENT-UNDER CAP
SCREW
GAS FLOW
IGNITOR
CONTROL
TO 24 V. THERMOSTAT
TO 24 V. COMMON ON TRANSFORMER
TO 24 V."HOT" ON TRANSFORMER
WIRING
I P-MODEL GAS VALVE AND WIRING
IGNITOR-PILOT ASSY.
FAN
SWITCH
MOTOR
HONEYWELL IP
SMART VALVE
120 VAC
LIMIT
CONTROL
VENT SAFETY
LIMIT
THERMOSTAT
40 VA TRANSFORMER
24 VAC
120VAC
VALVE CONTROL
CONNECTOR
L1 "HOT"
L2 NEUTRAL
LADDER WIRING DIAGRAM-IP VALVE
Figure 15