Empire Comfort Systems DVD36FP3 Indoor Fireplace User Manual


 
23552-1-0607Page 26
NOTE: Termination cap should pass through the wall firestop
from the exterior of the building. Adjust the termination
cap to its final exterior position on the building.
WARNING: Termination cap must be positioned so that arrow
is pointing up.
Attach the termination cap with the four wood screws provided.
Before attachment of the termination, run a bead of silicone sealant
rated above 250°F on its outside edge too, so as to make a seal to
the exterior wall.
NOTE: Wood screws can and should be replaced with appropriate
fasteners for use on stucco, brick, concrete or other types
of siding.
CAUTION: If exterior walls are finished with vinyl siding (or
materials that could become discolored or warp), it is necessary
to install the vinyl siding standoff SD-950.
Vinyl siding standoff SD-950 will be installed between the vent
termination and the exterior wall. (See Figure 42) This horizontal vent
termination bolts onto the flat portion of the vinyl siding standoff, so
an air space will exist between the wall and the termination cap.
Figure 42
For installations requiring a vertical rise on the exterior of the
building, 14-inch and 36-inch tall Snorkel Terminations, as
shown in Figure 43a are available. Follow the same installation
procedures as used for standard Horizontal Terminations. If the
Snorkel Termination must be installed below grade, (i.e. basement
application), proper drainage must be provided to prevent water
from entering the Snorkel Termination. Refer to Figure 43b. Do
not attempt to enclose the Snorkel within the wall or any other
type of enclosure.
12 INCHES
MINIMUM
SNORKEL
12 INCHES
MINIMUM
ADEQUATE
DRAINAGE
SNORKEL
Figure 43a
Figure 43b
HORIZONTAL TERMINATION