Emerson 2 Air Conditioner User Manual


 
Specifications
26
Table 13 Electrical data, 50 Hz - amps
Model Volts Phase
No Heat 5 kW Heat 10 kW Heat
15 kW Heat*
Circ1 Circ2
FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD
ET017H 220/240 1 12.8 15.1 20 23.4 29.3 30 44.4 55.5 60 NA
ET017S 220/240 1 13.8 16.3 25 23.4 29.3 30 44.4 55.5 60 NA
ET023H 220/240 1 13.7 16.2 25 23.4 29.3 30 44.4 55.5 60 NA
ET023S 220/240 1 15.2 18.1 30 23.4 29.3 30 44.4 55.5 60 NA
ET023H 380/415 3 5.9 6.9 15 8.3 10.4 15 15.3 19.1 20 NA
ET023S 380/415 3 6.3 7.4 15 8.3 10.4 15 15.3 19.1 20 NA
ET035H 220/240 1 20.3 24.4 40 23.4 29.3 40 44.4 55.5 60 44.4 55.5 60 21 26.3 30
ET035S 220/240 1 17.4 20.8 35 23.4 29.3 35 44.4 55.5 60 44.4 55.5 60 21 26.3 30
ET035H 200/230 3 15.2 18.1 30 15.2 18.1 30 26.4 33 35 38.4 48 50
ET035S 200/230 3 14.5 17.2 25 14.5 18 25 26.4 33 35 38.4 48 50
ET035H 380/415 3 6.8 8 15 8.3 10.4 15 15.3 19.1 20 22.3 27.9 30
ET035S 380/415 3 7.7 9.1 15 8.3 10.4 15 15.3 19.1 20 22.3 27.9 30
ET047S
ET347S
200/230 3 21.9 25.5 35 21.9 25.5 35 28.2 35.3 35 40.2 50.3 60
ET047S
ET347S
380/415 3 11 12.8 20 11 12.8 20 16.1 20.1 25 23.1 28.9 30
EF059S
ET359S
200/230 3 28.3 33.5 50 28.3 33.5 50 28.3 35.3 50 40.2 50.3 50
ET059S
ET359S
380/415 3 13.8 16.3 25 13.8 16.3 25 16.1 20.1 20 23.1 28.9 30
* 15 kW heat option @ 220/240 - 1 phase requires two electrical feeds.
Circuit 1 supplies the compressor, condenser, 10 kW heat and the evaporator motor.
Circuit 2 supplies the remaining 5 kW heat.