Emerson 2 Air Conditioner User Manual


 
Specifications
21
Table 7 Technical data, 60 Hz, continued
Model ET048, ET348 ET060, ET360
Compressor Type Scroll Scroll
Net capacity data based on 80°F (26.6°C) DB/67°F (19.4°C) WB indoor ambient - BTUH (kW)*
Outdoor ambient
85°F
(29.4°C)
Total 49100 (14.39) 58500 (17.14)
Sensible 39300 (11.51) 42800 (12.54)
95°F
(35.0°C)
Total 46900 (13.74) 56000 (16.41)
Sensible 38400 (11.25) 41900 (12.28)
105°F
(40.6°C)
Total 44500 (13.04) 53400 (15.65)
Sensible 37600 (11.02) 40900 (11.98)
115°F
(46.1°C)**
Total 42000 (12.31) 50500 (14.80)
Sensible 36700 (10.75) 39800 (11.66)
Net capacity data based on 75°F (23.9°C) DB/62.5°F (16.9°C) WB indoor ambient - BTUH (kW)*
Outdoor ambient
85°F
(29.4°C)
Total 46000 (13.48) 54900 (16.09)
Sensible 38200 (11.19) 41900 (12.28)
95°F
(35.0°C)
Total 43800 (12.83) 52400 (15.35)
Sensible 37300 (10.93) 40800 (11.95)
105°F
(40.6°C)
Total 41500 (12.16) 49800 (14.59)
Sensible 36300 (10.64) 39700 (11.63)
115°F
(46.1°C)**
Total 39200 (11.49) 47100 (13.80)
Sensible 35400 (10.37) 38600 (11.31)
Evaporator Air Flow - Dry Coil (Derate ESP by 0.2 - IN WG (50 Pa) for ET348 and ET360)
External Static Pressure CFM (m
3
/hr)
0.0 - IN WG (0.0 Pa) 2030 (3450) 2030 (3450)
0.1 - IN WG (25 Pa) 1910 (3240) 1910 (3240)
0.2 - IN WG (50 Pa) 1770 (3010) 1770 (3010)
0.3 - IN WG (75 Pa) 1650 (2800) 1650 (2800)
0.4 - IN WG (100 Pa) 1520 (2580) 1520 (2580)
0.5 - IN WG (125 Pa) 1390 (2360) 1390 (2360)
Evaporator Air Flow - Wet Coil (Derate ESP by 0.2 - IN WG (50 Pa) for ET348 and ET360)
External Static Pressure CFM (m
3
/hr)
0.0 - IN WG (0.0 Pa) 1800 (3060) 1800 (3060)
0.1 - IN WG (25 Pa) 1680 (2850) 1680 (2850)
0.2 - IN WG (50 Pa) 1580 (2680) 1580 (2680)
0.3 - IN WG (75 Pa) 1470 (2500) 1470 (2500)
0.4 - IN WG (100 Pa) 1360 (2310) 1360 (2310)
0.5 - IN WG (125 Pa) 1250 (2120) 1250 (2120)
Evaporator
Motor Hp (kW) 0.50 (0.37) 0.50 (0.37)
Filter Sizes - Quantity in. (cm)
21 x 36.25 x 2 - one
(53.3 x 92 x 5)
21 x 36.25 x 2 - one
(53.3 x 92 x 5)
Drain Connection - ID in. 3/8 3/8
Weight - w/o Economizer Ib/kg 470 (213) 470 (213)
Weight - with Economizer Ib/kg 490 (222) 490 (222)
* Based on rated airflow with no external static and no outside air.