Emerson 2 Air Conditioner User Manual


 
Specifications
25
Table 12 Electrical data, 60 Hz - amps
Model Volts Phase
No Heat 5 kW Heat 10 kW Heat
15 kW Heat*
Circ1 Circ2
FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD
ET018H 208/230 1 13.4 15.8 25 23.4 29.3 30 44.4 55.5 60 NA
ET018S 208/230 1 14.5 17.2 25 23.4 29.3 30 44.4 55.5 60 NA
ET024H 208/230 1 14.7 17.4 25 23.4 29.3 30 44.4 55.5 60 NA
ET024S 208/230 1 15.2 18.1 30 23.4 29.3 30 44.4 55.5 60 NA
ET024H 208/230 3 11.3 13.2 20 14.4 18 20 26.4 33 35 NA
ET024S 208/230 3 11.7 13.7 20 14.4 18 20 26.4 33 35 NA
ET024H 460 3 5.9 6.9 15 7.3 9.1 15 13.3 16.6 20 NA
ET024S 460 3 5.9 6.9 15 7.3 9.1 15 13.3 16.6 20 NA
ET036H 208/230 1 21.8 26.3 45 23.4 29.3 45 44.4 55.5 60 44.4 55.5 60 21 26.3 30
ET036S 208/230 1 19.5 23.4 40 23.4 29.3 40 44.4 55.5 60 44.4 55.5 60 21 26.3 30
ET036H 208/230 3 15.2 18.1 30 15.2 18.1 30 26.4 33 35 38.4 48 50
ET036S 208/230 3 15.2 18.1 30 15.2 18.1 30 26.4 33 35 38.4 48 50
ET036H 460 3 6.8 8 15 7.3 9.1 15 13.3 16.6 20 19.3 24.1 25
ET036S 460 3 7.7 9.1 15 7.7 9.1 15 13.3 16.6 20 19.3 24.1 25
ET048S
ET348S
208/230 1 31.9 38 50 31.9 38 50 46.2 57.8 60 46.2 57.8 60 21 26.3 30
ET048S
ET348S
208/230 3 21.9 25.5 35 21.9 25.5 35 28.2 35.3 35 40.2 50.3 60
ET048S
ET348S
460 3 11 12.8 20 11 12.8 20 14.1 17.6 20 20.1 25.1 30
ET060S
ET360S
208/230 1 37.7 45.2 60 37.7 45.2 60 46.2 57.8 60 46.2 57.8 60 21 26.3 30
ET060S
ET360S
208/230 3 28.3 33.5 50 28.3 33.5 50 28.3 35.3 50 40.2 50.3 50
ET060S
ET360S
460 3 13.8 16.3 25 13.8 16.3 25 14.1 17.6 25 20.1 25.1 30
* 15 kW heat option @ 208/230 - 1 phase requires two electrical feeds.
Circuit 1 supplies the compressor, condenser, 10 kW heat and the evaporator motor.
Circuit 2 supplies the remaining 5 kW heat.