EARTHSTONE OVENS PRE-ASSEMBLED INSTALLATION INSTRUCTIONS---U.L. LISTED 14
40” MIN
36” MIN
For Models 90 and 110
For Models 130 and 160
22”
10”
37”
Type-I Exhaust Hood Installed per NFPA 96
**IT IS NEVER APPROPRIATE TO USE “CLASS A” OR
“B VENT” IN ANY PART OF THE EXHAUST SYSTEM
EXHAUST SYSTEMS SERVING SOLID-FUEL
EQUIPMENT MAY NOT BE COMBINED WITH
EXHAUST SYSTEMS SERVING OTHER
(NON-SOLID FUEL) COOKING EQUIPMENT
Grease filters must be placed at the rear of the hood
and must be of the steel baffle t
y
pe
(
No mesh filters
)
.
Front of hood must be at least 10 inches from
the front of the oven face.
Face of the filter must be 42 inches from oven
hearth per UMC or 48 inches per NFPA 96
Sides of the hood must extend a min. of 6 inches to
either side of the oven door opening.
3 inch min. clearance between the hood and any
combustible material.
Grease filters