www.desatech.com
116646-01E 21
Figure 32 - Gas Connection
CSA Design-Certied
Equipment Shutoff Valve with
1/8" NPT Tap*
3" Minimum
Approved
Flexible Gas
Line
Cap Pipe Nipple Tee Joint
Sediment Trap/Drip Leg
Natural - From
Gas Meter (5.5"
W.C. to 10.5"
W.C. Pressure)
Propane/LP
From External
Regulator (11"
W.C. to 14"
W.C. Pressure)
* The CSA design-certied equipment shutoff
valve may be supplied with the appliance or you
can purchase it from your retailer.
We recommend that you install a sediment trap/drip
leg in supply line as shown in Figure 32. Locate
sediment trap/drip leg where it is within reach for
cleaning. Install in piping system between fuel
supply and replace. Locate sediment trap/drip
leg where trapped matter is not likely to freeze. A
sediment trap traps moisture and contaminants. This
keeps them from going into replace gas controls. If
sediment trap/drip leg is not installed or is installed
wrong, replace may not run properly.
FIREPLACE
INSTALLATION
Continued
Figure 33 - Connecting Flexible Gas Line
to Millivolt Valve
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping
and connections, internal and
external to unit, for leaks after
installing or servicing. Correct
all leaks at once.
WARNING: Never use an open
ame to check for a leak. Apply
noncorrosive leak detection uid
to all joints. Bubbles forming show
a leak. Correct all leaks at once.
PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect replace and its individual equip-
ment shutoff valve from gas supply piping
system. Pressures in excess of 1/2 psig (3.5 kPa)
will damage replace gas regulator.
2. Cap off open end of gas pipe where equipment
shutoff valve was connected.
3. Pressurize supply piping system by either
opening propane/LP supply tank valve for
propane/LP gas replace or opening main gas
valve located on or near gas meter for natural
gas replace or using compressed air.
4. Check all joints of gas supply piping system.
Apply noncorrosive leak detection uid to all
joints. Bubbles forming show a leak. Correct
all leaks at once.
5. Reconnect replace and equipment shutoff
valve to gas supply. Check reconnected ttings
for leaks.
Flexible Gas Line
Do NOT Kink
Equipment
Shutoff
Valve
To Gas Supply
(Natural)
To External
Regulator
(Propane/LP)
Control Valve
CONNECTING FIREPLACE TO GAS
SUPPLY
Installation Items Needed
• 5/16" hex socket wrench or nut-driver
• sealant (resistant to propane/LP gas, not pro-
vided)
1. Open lower louver door panel by gently
pulling forward.
2. Route exible gas line (provided by installer)
from equipment shutoff valve to replace.
Route exible gas supply line through one
of the access holes on side of replace.
3. Attach exible gas line from gas supply
to control valve (see Figure 33).
4. Check all gas connections for leaks. See
Checking Gas Connections.