Desa CD32M(-1)(-2) Indoor Fireplace User Manual


 
-4 - For more information, visit www.desatech.com
VENT PIPE AND TERMINATION CLEARANCES
The final position of your appliance depends on the location of the termination in relation to the clearances that must be observed.
A= 12” (305mm) clearance above grade, veranda, porch, deck
or balcony. ***
B= 9” (229mm) clearance in U.S. and 12” (305mm) clearance
in Canada to window or door that may be closed.
C= 9” (229mm) clearance in U.S. and 12” (305mm) clearance
in Canada to permanently closed window or door that maybe
opened.
D= 18” (475mm) vertical clearance to ventilated and 12”
(305mm) to unventilated soffit located above the terminal
within a horizontal distance of 2 feet (610mm) from the
centerline of the terminal.
E= 12” (305mm) clearance below eaves.
F= 9” (229mm) clearance to outside corner.
G= 6” (15mm) clearance to inside corner.
H= not to be installed above a meter/regulator within 3 feet
(914mm) horizontally from the centerline of the regulator. ***
I= 36” (914mm) clearance in U.S. and 72” (1829mm) in
Canada to service regulator vent outlet. ***
J= 12” (305mm) clearance to non-mechanical air supply inlet
to building or the combustion air inlet to any other
appliance.***
K= 36” (914mm) clearance to a mechanical air supply inlet.
L= 84” (2134mm) clearance above paved sidewalk or paved
driveway located on public property. *
M= 12” (305mm) clearance under veranda, veranda, porch,
deck or balcony. **
* vent shall not terminate directly above a sidewalk or paved driveway that is located between two single-family dwellings and serves
both dwellings.
** only permitted if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor.
*** as specified in CGA-B149 installation codes (1991) for Canada or for U.S. installation follow the current National Gas Code,
ANS Z223.1. Note: Local codes or regulations may require different clearances
.